Laserfiche WebLink
6FTTLFR4YAN INC. FORM 1 GR Job # 19200015 <br /> ^� <br /> SUMMARY OF SOURCE TEST DATA <br /> SOURCE INFORMATION FACILITY PARAMETERS <br /> GOF Name and Address GDF Representative and Title PHASE 11 SYSTEM TYPE <br /> Arco 2186 Daryl Lee (Check one) <br /> 3212 N California <br /> S tock ton , CA GDF Phone No . Balance <br /> 415 - 902 - 5089 Hirt <br /> Permit Condtions Source, GDF Vapor Recovery System Red Jacket <br /> VST Hasstech <br /> Healy <br /> GDF # Other <br /> A/C N Manifolded7 Yes Nd <br /> Operating Parameters <br /> Number of Nozzles Served by Tank #1 8 Number of Nozzles Served by Tank 143 8 <br /> Number of Nozzles Served by Tank #2 8 Number of Nozzles Served by Tank 04 <br /> Applicable Regulations : VR-203 -I and VR-2041 VN Recommended <br /> Source Test Results and Comments <br /> Tank # : 1 2 3 4 <br /> 1 , Product Grade 87 87 91 <br /> 2 . Actual Tank Capacity, gallons 20r000 10 , 000 12 , 000 <br /> 3 , Gasoline Volume Total 8984 510 0 3555 <br /> 4 . Ullage, gallons (## 243 ) 24093 10 , 719 5080 8294 <br /> 5 . Initial Pressure, inches H2O 2 v00 <br /> 6. Pressure After 1 Minute , inches H2O 2 ' 00 <br /> 7 . Pressure After 2 Minutes, inches H2O 2 . 00 <br /> Be Pressure After 3 Minutes , inches H2O 2 . 01 <br /> 9 . Pressure After 4 Minutes, inches H2O 2 . 01 <br /> 10 . Final Pressure After 5 Minutes, inches H2O 2 ' 01 <br /> 11 . Allowable Final Pressure 1 . 94 <br /> Test Conducted by : Test Company: Date of Test : <br /> David Rouse Gettler-Ryan Inc. <br /> 1 / 3 / 2019 <br /> California Air Resource Board March 17, 1999 <br /> TP -201 . 3, Page 14 <br /> i <br /> i' <br />