Laserfiche WebLink
DiETz ENGINEERING AND CoNsTR UCTiox INc- <br /> SERVING <br /> AGRICULTURE AND INDUSTRY <br /> CA Lic.#638281 <br /> EG vD <br /> JAN 0 8 2008 <br /> January 4, 2008 <br /> ENVIRONMENT HEALTH <br /> PERMIT/SERVICES <br /> San Joaquin Environmental Health Department �` 1' 0 "P <br /> Attn- Mike Huggins <br /> r 600-East Main Street" <br /> Stockton, CA 95202 <br /> Subject: Quarterly Inspection and Sampling of MicroSepTec System at Carmelo Business <br /> Park, Tracy, California <br /> Dear Mr. Huggins: <br /> A quarterly inspection of the MicroSepTec system installed at the Carmelo Business Park was <br /> conducted on December 12, 2007. The System was operating normally and no repairs were <br /> required. The meter reading for the effluent discharge was 1665060. Attached are the results of <br /> the laboratory analysis for nitrate. Based on laboratory results the calculation of the nitrogen in <br /> the effluent is as follows: 14/62x3.19=0.72 mg./L nitrogen as nitrate. Since this meets the <br /> design criteria of the system no further analysis or investigation was conducted. <br /> If you have any questions please contact me at the number listed below. <br /> Sincerely, <br /> H. B. Dietz <br /> BBD/gwd <br /> Enclosures: Laboratory Analysis <br /> 33233 S. Koster Road Tracy, CA 95304-9142 • (209) 832-2910 • Fax (209) 833-1288 <br />