Laserfiche WebLink
Lancaster <br /> Laboratories Analysis Report � <br /> 2425 New Holland Pike PO Boot 12425 Lancaster PA 17605-2425-717-656-2300 Fax 717-656-2681•www lancasterlabs cord <br /> Page 3 of 3 <br /> Quality Control Summary <br /> Client Name ChevronTexaco c/o Cambria Group Number 965815 <br /> Reported 11/15/05 at it 19 AM <br /> Surrogate Quality Control <br /> Batch number 053130003A <br /> Acetone <br /> 4638651 100 <br /> 4638652 98 <br /> 4638653 100 <br /> Blank 101 <br /> LCs 101 <br /> Ms 111 <br /> MSD 110 <br /> Limits 78-128 <br /> Analysis Name BTEX+MTBE by 8260B <br /> Batch number Z053112AA <br /> Dibromofluoromethane 1,2-Dichloroethane-d4 Toluene-d8 4-13romofluorobenzene <br /> 4638650 Be 82 91 85 <br /> Blank 90 83 92 84 <br /> LCS 88 83 91 66 <br /> MS 90 83 92 87 <br /> MSA 90 83 91 86 <br /> Limits 80-116 77-113 80-113 78-113 <br /> Analysis Name BTEX+5 Oxygenates+EDC+EDB4ETOH <br /> Batch number Z053113AA <br /> Aibromofluoromethane 1,2-Dichloroethane-d4 Toluene-dB 4-Bromofluorobenzene <br /> 4638651 89 79 87 63 <br /> 4638652 89 79 87 83 <br /> 4638653 89 79 87 84 <br /> Blank Be 80 86 83 <br /> LCS Be 7B 87 85 <br /> Ms B8 78 86 64 <br /> MSD Be 78 87 85 <br /> Limits 80-116 77-113 80-113 78-113 <br /> *-Outside of specification <br /> (1) The result for one or both determinations was less than five times the LOQ • <br /> (2) The background result was more than four times the spike added <br />