MEP COMPONENT ANCHORAGE NOTE PLUMBING LEGEND PLUMBING FIXTURE SCHEDULE
<br /> ALL MECHANICAL, PLUMBING AND ELECTRICAL COMPONENTS SHALL BE ANCHORED AND INSTALLED PER THE DETAILS ON THE DSA
<br /> SANITARY SEWER SS SUPPORT MATERIAL
<br /> APPROVED CONSTRUCTION DOCUMENTS. WHERE NO DETAIL IS INDICATED,THE FOLLOWING COMPONENTS SHALL BE ANCHORED OR ( ) FHC FERE HOSE CABINET SYMBOL MAKE NUMBER DESCRIPTIONITRIM
<br /> BRACED TO MEET THE FORCE AND DISPLACEMENT REQUIREMENTS PRESCRIBED IN THE 2016 CBC, SECTIONS 1616A.1.18 THROUGH -Y--- -- SANITARY VENT(V) FM FLOOR MOUNT
<br /> 1616A.1.26 AND ASCE 7-10 CHAPTER 13,26 AND 30. --- COLD WATER(CW) FSR FIRE SPRINKLER RISER WC-1 AMERICAN 3043.001 FLUSH VALVE WATER CLOSET WITH ELONGATED BOWL, FLOOR VIT.IT. CHINA
<br /> - HOT WATER (140° F)(HW) G GAS STANDARD MADERA 16-112" HIGH, FURNISH:AMERICAN STANDARD MOUNT
<br /> 1. ALL PERMANENT EQUIPMENT AND COMPONENTS. � SELECTRONIC 606B.121 SENSOR-OPERATED LOW
<br /> 2. TEMPORARY OR MOVABLE EQUIPMENT THAT IS PERMANENTLY ATTACHEDHARD WIRED TO THE BUILDING UTILITY - - HOT WATER RETURN (140°F HWR CONSUMPTION FLUSH VALVE(1.28 GPF), PK00.MAC POWER
<br /> (E.G.( ) )( ) G,RID GAS RISERIDROP
<br /> SERVICES SUCH AS ELECTRICITY, GAS OR WATER. A COMPRESSED AIR GCO GRADE CLEANOUT KIT, BENEKE 523SS OPEN FRONT WHITE SEAT, SUPPLY,
<br /> 3. MOVABLE EQUIPMENT WHICH IS STATIONED IN ONE PLACE FOR MORE THAN 8 HOURS AND HEAVIER THAN 40C POUNDS OR HASA ---AV--- ACID VENT(AV) GPR GAS PRESSURE REGULATOR AND STOP. ACCESSIBLE.
<br /> CENTER OF MASS LOCATED 4 FEET OR MORE ABOVE THE ADJACENT FLOOR OR ROOF LEVEL THAT DIRECTLY SUPPORT THE ---AW ACIDWASTE A
<br /> COMPONENT ARE REQUIRED TO BE ANCHORED WITH TEMPORARY ATTACHMENTS. ( �M GV GATE VALVE WC-2 AMERICAN 2234.001 FLUSH VALVE WATER CLOSET WITH ELONGATED BOWL, 15" FLOOR VIT. CHINA
<br /> cD CONDENSATE DRAIN GWH GAS WATER HEATER STANDARD MADERA HIGH, FURNISH:AMERICAN STANDARD SELECTRQNIC MOUNT
<br /> THE FOLLOWING MECHANICAL AND ELECTRICAL COMPONENTS SHALL BE POSITIVELY ATTACHED TO THE STRUCTURE, BUT THE D DRAIN LINE HW HOT WATER I 606B.121 SENSOR-OPERATED LOW CONSUMPTION FLUSH
<br /> ATTACHMENT NEED NOT BE DETAILED ON THE PLANS. THESE COMPONENTS SHALL HAVE FLEXIBLE CONNECTIONS PROVIDED F FIRE PROTECTIONVALVE(1.28 GPF), PKGO.MAC POWER KIT, BENEKE 523SS NICHOLS MELBURG & ROSSETTO
<br /> BETWEEN THE COMPONENT AND ASSOCIATED DUCTWORK, PIPING AND CONDUIT. HW,DIR HOT WATER DROP/RISER OPEN FRONT WHITE SEAT, SUPPLY,AND STOP. ARCHITECTS + ENGINEERS
<br /> G GAS(G) IE INVERT ELEVATION _ 300 Knollcrest Drive
<br /> A. COMPONENTS WEIGHING LESS THAN 400 POUNDS AND HAVE A CENTER OF MASS LOCATED 4 FEET OR LESS ABOVE THE MG-- GAS-MEDIUM PRESSURE MV MIXING VALVE WC-3 AMERICAN 2599.001 FLUSH VALVE WATER CLOSET WITH ELONGATED BOWL, 14" FLOOR VIT. CHINA Redding, CA, 96002
<br /> ADJACENT FLOOR OR ROOF LEVEL THAT DIRECTLY SUPPORT THE COMPONENT. - HP - GAS-HIGH PRESSURE (N) NEW STANDARD MADERA HIGH, FURNISH: SLOAN ROYAL153-1.28 WB CONCEALED MOUNTB. 530 222-3300 530 2 `'
<br /> YOUTH LOW CONSUMPTION FLUSH VALVE(1.28 GPF)WITH { ( 2� 3538 FAX
<br /> COMPONENTS WEIGHING LESS THAN 20 POUNDS,OR IN THE CASE OF DISTRIBUTED SYSTEMS, LESS THAN 5 POUNDS PER FOOT, p� �- RAIN WATER LEADER OVERFLOW(OF} NIPG NOT IN PLUMBING CONTRACT htt :1/www,nmrdesi n.com
<br /> WHICH ARE SUSPENDED FROM A ROOF OR FLOOR OR HUNG FROM A WALL. EASY-ACCESS WALL BOX, BENEKE 523SS OPEN FRONT ■ on.c-om
<br /> RWL --� RAIN WATER LEADER RWL
<br /> ( ) 01= OVER FLOW WHITE SEAT, SUPPLY,AND STOP.ACCESSIBLE. ■
<br /> FOR THOSE ELEMENTS THAT DO NOT REQUIRE DETAILS ON THE APPROVED DRAWINGS,THE INSTALLATION SHALL BE SUBJECT TO THE -SD - STORM DRAIN (SD) P&TRV PRESSURE&TEMP RELIEF VALVE REVISIONS
<br /> APPROVAL OF THE DESIGN PROFESSIONAL IN GENERAL RESPONSIBLE CHARGE OR STRUCTURAL ENGINEER DELEGATED -T TEMPERED WATER 110°F TW IMB-1 WATER- MODEL ICE MAKER CONNECTION BOX WITH FACTORY INSTALLED WALL Delta Description Date
<br /> RESPONSIBILITY AND THE DSA DISTRICT STRUCTURAL ENGINEER. THE PROJECT INSPECTOR WILL VERIFY THAT ALL COMPONENTS ( )( ) PC PLUMBING CONTRACTOR TITE W9700 CP VALVE, MOUNT @+12"ABOVE COUNTERTOP.
<br /> AND EQUIPMENT HAVE BEEN ANCHORED IN ACCORDANCE WITH ABOVE REQUIREMENTS TR -- TEMPERED WATER RETURN(110°F)(TWR) PRV PRESSURE REGULATING VALVE ADD 001 AD1 Incl/Reconcile 11.14.18
<br /> -WSP - WET STAND PIPE(WSP) PSI POUNDS PER SQUARE INCH UR-1 AMERICAN 5590.001 WASHOUT URINAL, FURNISH:AMERICAN STANDARD WALL VIT. CHINA Incl-2/Org.Apr. 1nc2
<br /> -® SHUT OFF VALVE IN VALVE BOX RD ROOF DRAIN STANDARD WASHBROOK 60613.013(0.125 GPF)SENSOR-OPERATED LOW - - - -
<br /> PIPING, DUCTWORK, AND „ELECT,RICAL DISTRIBUTION O GAS PRESSURE REGULATOR RWL RAIN WATER LEADER CONSUMPTION FLUSH VALVE, PKOO.MAC POWER KIT, RFI
<br /> SYSTEM BRACING NOTE e POINT OF CONNECTION RWL,D RAIN WATER LEADER DROP SUPPLY.AND STOP, COMMERCIAL CARRIER AND WALL
<br /> CLEANOUT, MOUNTING HEIGHT PER ARCHITECTURAL _ -
<br /> SOC SHUT OFF COCK PLANS.ACCESSIBLE. _
<br /> PIPING, DUCTWORK,AND ELECTRICAL DISTRIBUTION SYSTEMS SHALL BE BRACED TO COMPLY WITH THE FORCES AND DISPLACEMENTS ABC ABOVE CEILING SOV SHUT OFF VALVE L_1 AMERICAN 0700.004 LAVATORY,18-3I4"x 23-118" RECTANGLE, FAUCET HOLES ON COUNT
<br /> PRESCRIBED iN ASCE 7-10 SECTION 13.3 AS DEFINED IN ASCE 7-10 SECTION 13.6-5.6, 13.6.7, 13.6.8,AND 2016 CBC,SECTIONS 1616A.1.24, ADA AMERICAN DISABILITIES ACT TP(C) TRAP PRIMER (CONNECTION) STANDARD " ER VIT. CHINATOWN 4 CENTERS. CHICAGO 420-T45E39VPABCP SINGLE-HANDLE
<br /> 616A.1.25 AND 1616A.1.26. AFF ABOVE FINISH FLOOR TW TEMPERED WATER SQUARE MIXING FAUCET(0.35GPM). P-TRAP, SUPPLIES AND STOPS.
<br /> HE METHOD OF SHOWING BRACING AND ATTACHMENTS TO THE STRUCTURE FOR THE IDENTIFIED DISTRIBUTION SYSTEM AREAS NOTED AFG ABOVE FINISH GRADE TW,DIR TEMPERED WATER DROP/RISER ACCESSIBLE.
<br /> BELOW. WHEN BRACING AND ATTACHMENTS ARE BASED ON A PREAPPROVED INSTALLATION GUIDE(E.G.,SMACNA OR OSHPD OPM), BFF(G) BELOW FINISH FLOOR(GRADE) TYP TYPICAL -.
<br /> COPIES OF THE BRACING SYSTEM INSTALLATION GUIDE OR MANUAL SHALL BE AVAILABLE ON THE JOBSITE PRIOR TO THE START OF AND BV BALL VALVE OF UNDER FLOOR L-2 AMERICAN 0355.012 LAVATORY, 20-112"x 18-114", FAUCET HOLES ON 4" WALL VIT. CHINA
<br /> DURING THE HANGING AND BRACING OF THE DISTRIBUTION SYSTEMS THE STRUCTURAL ENGINEER OF RECORD SHALL VERIFY THECD CONDENSATE DRAIN US UNDER SLAB STANDARD LUCERNE CENTERS, CHICAGO 3400-ABCP METERING MIXING _.
<br /> -
<br /> ADEQUACY OF THE STRUCTURE TO SUPPORT THE HANGER AND BRACE LOADS. FAUCET, SET FAUCET CYCLE TIME AT 24 SECONDSCD,D CONDENSATE DRAIN DROP VB VALVE BOX MAXIMUM (02 GALLONS PER CYCLE). PROVIDE P-TRAP,
<br /> MECHANICAL PIPING(MP), MECHANICAL DUCTS(MD), PLUMBING PIPING(PP), ELECTRICAL DISTRIBUTION SYSTEMS (E): CE CIVIL ENGINEER V VENT SUPPLIEST STOPS CONCEALED ARMS AND
<br /> FLOOR-MOUNTED
<br /> UPRIGHTS WITH
<br /> M❑ MD❑ PP� E❑ OPTION 1: DETAILED ON THE APPROVED DRAWINGS WITH PROJECT SPECIFIC NOTES AND Cl CAST IRON V,R VENT RISER -
<br /> DETALS
<br /> CO CLEAN OUT VTR VENT THRU ROOF "LEONARD"MODEL 170-LF-BP-BRKT THERMOSTATIC
<br /> MP❑ Ml PP❑ EE] OPTION 2: SHALL COMPLY WITH THE APPLICABLE OSHPD PRE-APPROVAL(OPM#) CW COLD WATER WCO WALL CLEANOUT MIXING VALVE, INTEGRAL CHECK VALVES, MOUNTING -- - -
<br /> # CW,D/R COLD WATER DROP/RISER SS SANITARY SEWER BRACKET, LEAD FREE, 0.25 GPM MIN. FLOW, LOCKING
<br /> DSP DRY STAND PIPE SS,D SANITARY SEWER DROP TEMPERATURE REGULATOR, 318" INLETS, 318"OUTLET, SET -
<br /> MP❑ MD❑ PP❑ OPTION 3: SHALL COMPLY WITH THE SMACNA SEISMIC RESTRAINT MANUAL,OSHPD EDITIONATA MAX. TEMP, OF 120° F
<br /> ( - -
<br /> (2009), INCLUDING ANY ADDENDA, FASTENERS AND OTHER ATTACHMENTS NOT SPECIFICALLY (E) DRY STAND PIPE RISER WHA WATER HAMMER ARRESTOR
<br /> IDENTIFIED IN THE SMACNA SEISMIC RESTRAINT MANUAL,OSHPD EDITION,ARE DETAILED ON THE EJ EXISTING WM WALL MOUNT MS-1 FIAT TSB 100 24"x24"x 12" HIGH TERRAZZO MOP SINK WITH INTEGRAL FLOOR TERRAZZO
<br /> APPROVED DRAWINGS WITH PROJECT SPECIFIC NOTES AND DETAILS. THE DETAILS SHALL EWH ELECTRIC WATER HEATER WSP WET STAND PIPE STAINLESS STEEL CAP (ALL SIDES), INTEGRAL FLOOR
<br /> ACCOUNT FOR THE APPLICABLE SEISMIC HAZARD LEVEL-AND CONNECTION LEVEL_FOR FA FROM ABOVE WSP,R WET STAND PIPE RISER DRAIN. FURNISH: FIAT 830AA WALL MOUNTED H & CW
<br /> THE PROJECT AND CONDITIONS. FB FROM BELOW FAUCET WITH VACUUM BREAKER, ADJ. WALL BRACE, l _
<br /> SPOUT WITH HOSE THREAD, 830-AA HOSE & HOSE -
<br /> FCO FLOOR CLEANOUT BRACKET, 1453-BB STRAINER, P-TRAP, SUPPLIES AND
<br /> FFE FINISHED FLOOR ELEVATION STOPS.
<br /> ACORN 8151 HOSE BIBB WITH INTEGRAL VACUUM BREAKER,STAINLESS WALL STAINLESS STEEL
<br /> - STEEL RECESSED BOX WITH KEY If drawing is not 42"x 30" it is a reduced print
<br /> �-+
<br /> HB-2 ■ ■
<br /> PLUMBING GENERAL NOT ACORN 8126 HOSE BIBB WITH INTEGRAL VACUUM BREAKER. ROOF ROUGH BRONZE Copyright © 2017
<br /> E S All ideas,designs,arrangements and plans indicated or represented by
<br /> EQUIPMENT SCHEDULE this drawing are owned by,and the property of,NICHOLS,MELBURG
<br /> and RpS5ET C)and were created,evolved and developed for use on,
<br /> and in conjunction with,the specified project.None of such ideas,
<br /> TED-1 ZURN Z41513-P FLOOR DRAIN FOR CONCRETE FLOOR SEE PLAN FOR CAST IRON BODY designs,arrangements or plans shall be used by,or disclosed to any
<br /> SYMBOL MAKE NUMBER DESCRIPTIONITRIM SUPPORT NOTES 1. ALL FIXTURES WHITE UNLESS OTHERWISE NOTED. ( FLOOR
<br /> m
<br /> SIZE}WITH TRAP PRIMER CONNECTION, CAST IRON WITH NICKEL-BRONZE person,tirorcorporationforanypurpo5ewhaisoeverwithoutme
<br /> STRAINER written permission of NICHOLS,MELBURG and ROSSET o,
<br /> -- --TRA p. � ■
<br /> 2. PROVIDE FLOW CONTROL DEVICES ON LAVS AND SINKS PER T-24, PART 5, CCR. DW ZURN CD3P DISHWASHER NOT IN PLUMBING CONTRACT. PROVIDE AIR LICENSE
<br /> GWH A.O. SMITH BTX-80 55-112" HIGH X 27-314"DIAMETER CONDENSING GAS WATER FLOOR ----- STAMPS
<br /> HEATER, 50 GALLON CAPACITY, 120,000 BTUH NATURAL GAS 3. ALL F GAP FITTING AT ADJACENT SINK LEDGE.
<br /> FIXTURES SHALL BE FURNISHED WITH STOP VALVES.VALVES MAY BE IN SUPPLY PIPES OR
<br /> INPUT, 173 T 1 RECOVERY AT 80° F. TEMP. RISE DIRECT INTEGRAL WITH SUPPLY FITTINGS. SS_1 ELKAY LRAD0191865 19"x18"x6-112" DEEP, 18 GA., SINGLE COMPARTMENT COUNTER STAINLESS OF ESS
<br /> - VENT. SET AT 140°F. MAX. OPERATING WT. =961 LBS., SELF-RIMMING FULLY UNDERCOATED, STAINLESS STEEL STEEL k� QR TIC
<br /> I�y91
<br /> 120V-SINGLE PHASE, 5 AMPS. 4. PLUMBING CONTRACTOR SHALL COORDINATE ALL PLUMBING LINE LOCATIONS WITH OTHER TRADES. R cy
<br /> SINK, PUNCHED WITH 3 FAUCET HOLES. FURNISH: �� P� F4-
<br /> 5. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATION OF FIXTURES AND MOUNT NG HEIGHTS. CHICAGO W4D-L9E35-317ABCP(1.5 GPM) H&CW MIXING
<br /> 0_q_2
<br /> A.Q. SMITH 13TH-120 76-112" HIGH X 27-314" DIAMETER CONDENSING GAS WATER FLOOR ---- FAUCET SWING SPOUT, LK-35L DRAIN SYSTEM, P-TRAP, r M31176 ,yr"
<br /> HEATER, 100 GALLON CAPACITY, 150,000 BTUH NATURAL
<br /> XI 12/31119
<br /> E
<br /> GAS INPUT, 223 GPH RECOVERY AT 80° F. TEMP. RISE, . PLUMBING CONTRACTOR SHALL OBTAIN ALL NECESSARY PERMITS AND PAY ALL COSTS INVOLVED. SUPPLIES AND STOPS. � � �,,L �
<br /> f
<br /> DIRECT VENT, SET MAX. OPERATING WT. = 135$ tij- AN�Go��\P
<br /> LBS., 120V SINGLE PHHASESE 5 5 AMPS. 7 SS_2 CHICAGO 927-317XKCP INTEGRAL SINK BY ARCHITECTURAL, FAUCET ONLY: COUNTER STAINLESS ,0
<br /> INSULATE HOT&COLD WATER SUPPLY PIPES, STOPS, P-TRAP AND DRAIN LINE AT EACH ADA �1F
<br /> _ LAVATORY AND SINK WITH ANTI-MICROBIAL, SEAMLESS, VANDAL RESISTANT PROTECTIVE PIPE COVER SINGLE HOLE COLD WATER ONLY, GOOSENECK SPOUT, STEEL OF CA
<br /> "PROWRAP"OR EQUAL. LABORATORY NOZZLE. 6/10/2019 10:47:31 AM
<br /> IEWH CHRONOMITE SR-20LI INSTANTANEOUS ELECTRIC WATER HEATER WITH 71°F. WALL -
<br /> 1 208 TEMPERATURE RISE ATA GPM FLOW RATE, DIGITAL 8. ALL PIPE PENETRATIONS THROUGH ROOF SHALL BE FLASHED SIMILAR TO VTR'S. S-3 ELKAY LRAD291865 29"x18"x6-112"DEEP, 18 GA., DOUBLE COMPARTMENT COUNTER STAINLESS
<br /> _ MICROPROCESSOR, SET AT 110 DEGREES FAHRENHEIT, SELF-RIMMING FULLY UNDERCOATED, STAINLESS STEEL STEEL ■ ■
<br /> 4,160 WATTS,208 VOLT, 1 PHASE, 20 AMPS(5 LBS.) 9, ALL SANITARY SEWER VENT PIPE PENETRATIONS THROUGH ROOF SHALL TERMINATE AT A MINIMUM SINK, PUNCHED WITH 3 FAUCET HOLES. FURNISH: KEY PLAN
<br /> DISTANCE OF 10'FROM ANY FRESH AIR INTAKE. CHICAGO W4D-L9E35-317ABCP (1.5 GPM) H & CW MIXING
<br /> CH TOPS.HAWS 9321.9 INSTANTANEOUS ELECTRIC WATER HEATER WITH 16° F. WALLFAUCET, SWING SPOUT, LK-35L DRAIN SYSTEM, P-TRAP,
<br /> SUPPLIES AND S TEMPERATURE RISE AT 23 GPM FLOW RATE, DIGITAL 10, MINIMUM LOCAL CONNECTION SIZES SHALL BE MADE IN ACCORDANCE WITH THE SCHEDULE OF --� �\
<br /> MICROPROCESSOR,SET AT 75 DEGREES FAHRENHEIT, CONNECTIONS. iMTFrFFT7MTfttttf
<br /> RD1OFD-1 h \ u
<br /> W, V 3 S 50 SIP S 5 L ZURN 2165 COMBINATION ROOF AND OVERFLOW DRAINS WITH ROOF CAST
<br /> 11. ALL WATER PIPING SIZED IN ACCORDANCE WITH 2016 C.P.C. COMBINATION MEMBRANE FLASHING CLAMP/GRAVIE,L IRON
<br /> CHRONOMITE M 40L1 INSTANTANEOUS ELECTRIC WATER HEATER WITH 57° F. GUARDS, SUMP RECEIVER AND CAST IRON DOME 1
<br /> IEWH\ WALL o -� o
<br /> 3 / 208 TEMPERATURE RISE AT 1 GPM FLOW RATE, DIGITAL
<br /> FS-1 ZURN ZN-1901-2- FLOOR SINK WITH 112 GRATE, 12 112"SQUARE WITH DOME FLOOR CAST J
<br /> MICROPROCESSOR,SET AT 105 DEGREES FAHRENHEIT, 12. GAS PIPING SIZED IN ACCORDANCE WITH TABLE 1216.2, 2016 C.P.C.
<br /> 8,320 WATTS,208 VOLT, 1 PHASE 40 AMPS (5 LBS.} KC-P STRAINER. FURNISH:CAST IRON P-TRAP. SEE PLAN FOR IRON z
<br /> SIZE. MOUNT FLUSH WITH FLOOR. (TRAP PRIMER '
<br /> 8 _ r
<br /> OC� o
<br /> CONNECTION ONLY WHERE SHAWN ON PLANS-)
<br /> m „'
<br /> EW I ---- 13. ALL WASTE, WATER, FIRE AND STORM DRAIN PIPING SHALL BE STUBBED OUTSIDE BUILDING TO
<br /> 1 10 GALLON CAPACITY, 12 GPH RECOVERY AT 100° F. TEMP. CONNECTION POINT SHOWN. SEE CIVIL DRAWINGS FOR CONTINUATION. PLUMBING CONTRACTOR Jyo
<br /> RISE, RATED AT 3KW AT 208 VOLT, FED AT 208 VOLTS, 1 SHALL MAKE FINAL CONNECTIONS TO SITE PIPING.
<br /> FS-2 ZURN Z-1926-P-3-C FLOOR SINK WITH 314 GRATE, 16"SQUARE WITH DOME FLOOR CAST
<br /> PHASE,WITH P&TRV. (OPERATING WT. =200 LBS.) STRAINER, FURNISH: CAST IRON P-TRAP. SEE PLAN FOR IRON
<br /> 14. COORDINATE ALL TRENCHING WITH GENERAL CONT SIZE. MOUNT FLUSH WITH FLOOR. TRAP PRIMER
<br /> GI JENSEN HJ5000 PRE-CAST CONCRETE, 500 GALLON CAPACITY, _ CONTRACTOR.
<br /> 1 CONTRACTOR SHALL PROVIDE EXTENSIONS AS REQUIRED, CONNECTION ONLY WHERE SHOWN ON PLANS.) ■
<br /> GREASE INTERCEPTOR SHALL BE SUITABLE FOR SITE SOIL 15. ALL HOSE BIBBS SHALL BE 314"AND MOUNTED AT 12"ABOVE FINISHED FLOOR UNLESS OTHERWISE ■
<br /> CONDITIONS AND MEET REQUIREMENTS OF LOCAL NOTED. ALL HOSE BIBBS SHALL HAVE A NON-REMOVABLE VACUUM BREAKER. WHA MIFAB MWH PISTON OPERATED WATER HAMMER ARRESTER. SIZE AS STAINLESS STEEL PROJECT NAME
<br /> JURISDICTION.
<br /> 16. PLUMBING CONTRACTOR SHALL VERIFY LOCATION AND ADEQUACY OF SIZE AND DEPTH OF EXISTING RECOMMENDED BY MANUFACTURER. CORDES��++ELEMENTARY
<br /> GI JENSEN JP320EE-G PRE-CAST CONCRETE, 320 GALLON CAPACITY, _ PLUMBING UTILITIES PRIOR TO COMMENCEMENT OF ANY WORK OR ORDERING ANY MATERIALS. TMV-1 LEONARD 370-LF-BRKT THERMOSTATIC MIXING VALVE, INTEGRAL CHECK VALVES, SL+H OO L
<br /> 2 CONTRACTOR SHALL PROVIDE EXTENSIONS AS REQUIRED, 17 MOUNTING BRACKET, LEAD FREE, 0.5 GPM MIN. FLOW, WALL BRONZE
<br /> PROVIDE MATT=RIALS AND INSTALL IN ACCORDANCE WITH 2016 CALIFORNIA PLUMBING CODE AND
<br /> GREASE INTERCEPTOR SHALL BE SUITABLE FOR SITE SOIL LOCKING TEMPERATURE REGULATOR, 314"INLETS, 314" FOR
<br /> CONDITIONS AND MEET REQUIREMENTS OF LOCAL STATE CODE REGULATIONS. OUTLET, SET ATA MAX.TEMP, OF 120°F
<br /> JURISDICTION. 18. SEISMIC SUPPORTS AND BRACING FOR ALL PIPING SHALL BE FURNISHED AND INSTALLED IN EWC-1DUAL HEIGHT ELECTRIC WATER ELKAY VRCTL8W5K R COOLER WITH BOTTLE ■
<br /> ACCORDANCE WITH CBC SECTION 1613A,ASCE?SECTION 13.6.1 AND NFPA 13 STANDARDS FOR FILLER, 115V-10, 370 WATTS, 8.0 GPH AT 50 DEGREE WALL STAINLESS La m m e rsv�I I e
<br /> DSP IN-SINK EVOLUTION DISPOSER: CONTINUOUS FEED, 314 HP, CAPACITOR - STAINLESS STEEL SUPPORT AND ANCHORAGE. METHODS AND MATERIALS PUBLISHED BY SMACNA AND APPROVED BY FAHRENHEIT ACCESSIBLE, OPERATING WT. = 120 LBS. STEEL
<br /> 1 1=RATOR ESSENTIAL START. INSTALL DISPOSER IN RIGHT HAND STATE AGENCIES SHALL BE USED. BASIN
<br /> COMPARTMENT. PROVIDE WALL SWITCH FOR Unified S c h o o l
<br /> OPERATION AND PROVIDE FULL 6 YEAR PARTS AND RR-1 JAY R. SMITH 3960 DECK MOUNTED CAST IRON ROOF RECEPTOR, 7-114"TOP DECK CAST IRON
<br /> SERVICE WARRANTY 19. THE CONDENSATE DRAIN RECEPTACLE(CDR)AND ASSOCIATED WASTE AND VENT PIPING IS NOT DIAMETER, 2"DIAMETER DRAIN,APPROX. 16 LBS.� D ■
<br /> REQUIRED AT SITES WHERE THE ROOF DRAINS CONNECT TO A STORM DRAIN SYSTEM. CD LINES FROM _ District
<br /> CP CIRCULATION PUMP,ALL BRONZE CONSTRUCTION, 39 ROOFTOP MECHANICAL EQUIPMENT MAY SPILL OVER ROOF DRAINS W - -
<br /> WITH A TURNED DOWN ELBOW. DN 1 ZURN 2199-SS DOWNSPOUT NOZZLE FOR RAINWATER LEADER OVER FLOW PIPE PIPE NICKEL BRONZE
<br /> B&G NBF-8SILW WATTS, 115 VOLTS, 1 PHASE. 2.1 GPM, 5' HEAD. TC-1 TIMER
<br /> KIT, AQ-314 AQUASTAT. 20. THE WATER CLOSET CONTROLS (FLUSH HANDLE)MUST BE LOCATED ON THE CLEAR/WIDE SIDE OF TP-1 P.P.P. P2-500 ADJUSTABLE TRAP PRIMER VALVE WITH UNION AND BALL BRASS Mountain House, California
<br /> -� THE ACCESSIBLE WATER CLOSETS. VALVE ■
<br /> NOTE: FOR CONDENSING WATER HEATERS, PROVIDE FACTORY CONDENSATE NEUTRALIZING KIT,
<br /> ■
<br /> 21. HAZARDOUS AND COMBUSTIBLE MATERIAL LINES(E.G. GAS LINES) GREATER THAN 1" IN DIAMETER AND AD ELMDQR DW14X14 14"x 14"WALL ACCESS DOOR WITH CYLINDER LOCK. WALL STAINLESS STEEL SHEET TITLE
<br /> NON-HAZARDOUS LINES(E.G. WATER LINES) GREATER THAN 3" IN DIAMETER REQUIRE SEISMIC CL-5S
<br /> BRACING PER 2016 CBC SECTION 1616A.1.26,ACCEPTABLE SEISMIC BRACING DETAILS INCLUDE THOSE - - -
<br /> SHOWN IN THE EATON/COOPER B-LINE OPM-0052-13 WITH 2016 REVISIONS. GENERAL CONTRACTOR TO EEWIESH-1 HAWS 8356WCC EMERGENCY SHOWER AND EYE/FACE WASH, FLOOR
<br /> CONFIRM BRACING DETAILS WITH DESIGN TEAM PRIOR TO INSTALLATION. CHROME-PLATED BRASS PULL-DOWN EYE/FACE WASH SYMBOLS 4& NOTES I OTE�+
<br /> VALVE WITH EASY ACCESS IN-LINE STRAINER, STAINLESS �V S
<br /> STEEL SHOWER HEAD WITH BRASS STAY-OPEN BALL
<br /> VALVE AND PULL-DOWN ACTIVATION BAR. "HAWS"9201E
<br /> THERMOSTATIC MIXING VALVE, SET AT 85° FAHRENHEIT. ■
<br /> PLUMBING FIXTURE CONNECTIONS ■
<br /> _ DRAINING STATUS
<br /> WASTE COLD WATER HOT WATER
<br /> FIXTURE SYMBOL CONSTRUCTION
<br /> BRANCH OUTLET VENT TRAP BRANCH OUTLET BRANCH OUTLET
<br /> DOCUMENTS
<br /> WATER CLOSET WC 4" "
<br /> E 4 211
<br /> 1-112" 1" ■
<br /> 11
<br /> o ■
<br /> UL 2" 1-112" 1 112" 1-912" 112" 318" 112" - AGENCY APPROVAL
<br /> LAVATORY
<br /> L 318"
<br /> aw
<br /> ai URINAL UR 2" 2" 1-112" 1-1I2" 314"
<br /> 0 FLOOR DRAIN (1) Ip FD 2" 2" 1 112" 2" 112" 112" - --
<br /> O 3" 112" 1I2"
<br /> Q FLOOR SINK 1 FS 3" 3" 2° -
<br /> z
<br /> SERVICE SINK [� SS 2" 2" 1-112" 2" 314" 112"
<br /> 0 314" 112"
<br /> o SHOWER SH 2" 2" 1-112" 2" 314" 112" 314" 112"
<br /> U
<br /> �
<br /> ELECTRIC ❑ EWC 2" 1-114" 1-112" 1-112" 112" 112"
<br /> n WATER COOLER --
<br /> Lu
<br /> 73
<br /> HOSE BIBB °-- HB 314" 314"
<br /> ■ ■
<br /> °' NOTES: .�
<br /> Drawn By EP
<br /> Q
<br /> D
<br /> (1) TPC ONLY WHERE NOTED ON PLANS
<br /> � o
<br /> Date Issued 09.21.2018
<br /> m 0
<br /> O O
<br /> Scale
<br /> Y' L
<br /> o �
<br /> Project No.
<br /> O
<br /> N � ■ ■
<br /> O(__
<br /> U
<br /> a�
<br /> 2411 Alhambra Blvd Ste. 100 SHEET No.
<br /> Tel (916) 447-2841
<br /> o e Sacramento, CA 95817
<br /> o
<br /> E: LEE engineering
<br /> PETERS wwW.peterseng.com
<br /> Job no. 1 7,1 1 0 Pool
<br /> consulting mechanical and electrical engineers ■ ■ ■
<br />
|