260500 ELECTRICAL WORK FOR COMMON RESULTS:
<br /> 260550. WIRING METHODS: LINE VOLTAGE SYSTEMS (120V AND ABOVE): 9. CONDUITS SHALL BE SUPPORTED WITH STRAPS, WITH GALVANIZED MALLEABLE SPLIT RING AND
<br /> 1. ELECTRICAL INSTALLATION SHALL COMPLY WITH TITLE 24, CALIFORNIA ROD FOR INDIVIDUAL RUNS OR WITH KINDORF OR UNISTRUT CHANNEL SUPPORTS FOR MULTIPLE RUNS.
<br /> CODE OF REGULATIONS, INCLUDING THE FOLLOWING: 1. ALL WIRING SHALL BE INSTALLED IN CONDUITS. CONDUITS SHALL BE RUN CONCEALED IN WALLS DISTANCE BETWEEN SUPPORTS SHALL NOT EXCEED 10 FEET. CONDUITS SHALL BE SUPPORTED
<br /> TITLE 24, CCR, PART 2, 2016 CBC AND CEILINGS WHERE FEASIBLE. ALL CONDUITS INSTALLED SURFACE ON WALL SHALL BE PAINTED TO INDEPENDENTLY OF ONE ANOTHER.
<br /> TITLE 24, CCR, PART 3, 2016 CEC MATCH WALL FINISH. MOUNT EXTERIOR CONDUITS ON WALL ON GALVANIZED UNISTRUTS. ALL SURFACE
<br /> TITLE 24, CCR, PART 4, 2016 CMC CONDUIT INSTALLATION/RUNS SHALL BE APPROVED BY THE ARCHITECT PRIOR TO INSTALLATION. 10. CONDUITS CONNECTED TO BOXES AND CABINETS SHALL BE FITTED WITH TWO LOCKNUTS AND
<br /> TITLE 24, CCR, PART 9, 2016 CFC INSULATED BUSHING, OA"A" SERIES.
<br /> A
<br /> TITLE 24, CCR, PART 6, 2016 CALIFORNIA ENERGY CODE 2. ALL CONDUITS RUN WITHIN INTERIOR FINISHED SPACES SUCH AS OFFICES, BREAKROOM,
<br /> TITLE 24, CCR, PART 11, 2016 CALIFORNIA GREEN BUILDING STANDARDS CODE RESTROOM ETC. SHALL BE RUN CONCEALED. 11. CONDUITS NOT CONNECTED WITH LOCKNUTS AND BUSHINGS SHALL BE FITTED WITH GROUNDING
<br /> ALL APPLICABLE LOCAL CODES BUSHING, OZ "BL" SERIES, U. L. APPROVED AND BONDED.
<br /> 3. ALL CONDUITS RUN IN DEDICATED ELECTRICAL AND MECHANICAL ROOMS SHALL BE RUN
<br /> 2. ELECTRICAL CONTRACTOR SHALL VERIFY POWER, TELEPHONE AND CABLE TV SERVICES AT SITE PRIOR EXPOSED. 12. CONDUIT STRAPS FOR INDIVIDUAL RUNS SHALL BE SECURED BY TOGGLE BOLTS ON HOLLOW
<br /> TO BIDDING. SERVICES TO CONFORM TO UTILITY COMPANY REQUIREMENTS. ELECTRICAL CONTRACTOR MASONRY, EXPANSION ANCHORS ON SOLID CONCRETE OR MASONRY, MACHINE SCREWS OR BOLTS ON
<br /> SHALL ARRANGE FOR SERVICE INSTALLATIONS PER UTILITY COMPANY REQUIREMENTS AND PAY ALL 4. MINIMUM CONDUIT SIZE SHALL BE 1/2"ABOVE GRADE AND 3/4" UNDERGROUND. METAL SURFACES AND WOOD SCREWS ON WOOD CONSTRUCTION. THE USE OF NAILS TO ANCHOR
<br /> CUSTOMER CHARGED SERVICE COSTS. COORDINATE WITH OWNER AND UTILITY COMPANY FOR SERVICE STRAPS ON WOOD CONSTRUCTION IS PROHIBITED. STRAPS SHALL BE TWO HOLE MALLEABLE IRON OR Architect:
<br /> INSTALLATION. 5. MINIMUM ACCEPTABLE CONDUITS ARE: SNAP-TYPE STEEL WITH RIBBED BACK, GALVANIZED OR CADMIUM PLATED. THE USE LDA Partners, LLP
<br /> 3. CONTRACTOR SHALL PROCURE AND PAY FOR ALL PERMITS, LICENSES, ETC. REQUIRED TO CARRY ON A. GALVANIZED RIGID STEEL- FOR USE ON: 13. PLACEMENT OF ALL BOXES SHALL BE GOVERNED BY APPLICABLE ARCHITECTURAL AND Designers & Architects
<br /> AND COMPLETE THE WORK. (1) EXTERIOR WALL SURFACES. STRUCTURAL REQUIREMENTS. 222 Central Court
<br /> Stockton, CA 95204
<br /> 4. PROVIDE ALL LABOR, MATERIALS, TOOLS, PLANT EQUIPMENT, TRANSPORTATION AND PERFORM ALL B. GALVANISED STEEL EMT FOR USE: 14. CONDUIT FITTINGS: EXCEPT WHERE OTHERWISE NOTED, CONDUIT FITTINGS SHALL BE APPLETON 209.943.0405
<br /> OPERATIONS NECESSARY FOR ANY REASONABLE INCIDENTAL TO PROPER EXECUTION AND COMPLETION (1) CONCEALED IN INDOOR FINISHED SPACES. OR APPROVED EQUAL. UNILETS SHALL BE MALLEABLE IRON AND FITTED WITH COVERS AND GASKETS.
<br /> OF ALL"ELECTRICAL WORK"WHETHER SPECIFICALLY MENTIONED OR NOT; ALL AS INDICATED, SPECIFIED (2) EXPOSED INSIDE ELECTRICAL& MECHANICAL ROOMS. www.ldapartners.com
<br /> HEREIN, AND/OR IMPLIED THEREBY TO CARRY OUT THE APPARENT INTENT THEREOF. 15. TELEPHONE AND SIGNAL CONDUIT BENDS WHERE REQUIRED SHALL HAVE A RADIUS OF TEN TIMES
<br /> C. LIQUID TIGHT STEEL FLEX: THE CONDUIT TRADE SIZE.
<br /> 5. ALL MATERIALS SHALL BE NEW AND LISTED WITH THE UNDERWRITERS' LABORATORIES, INC., SHALL (1) FOR FINAL CONNECTION TO OUTDOOR EQUIPMENT. LENGTH SHALL NOT EXCEED 36".
<br /> MEET THEIR REQUIREMENTS AND SHALL BEAR THEIR LABEL WHEREVER STANDARDS HAVE BEEN 16. PROVIDE PULL TAPE IN ALL EMPTY CONDUITS.
<br /> ESTABLISHED AND LABEL SERVICE IS REGULARLY FURNISHED BY THAT AGENCY. D. FLEXIBLE STEEL CONDUIT:
<br /> (1) FOR INDOOR FINAL CONNECTION TO RECESSED LIGHT FIXTURES. LENGTH SHALL NOT EXCEED 72". 260553. NAMEPLATES & IDENTIFICATION:
<br /> 6. ELECTRICAL DRAWINGS ARE ESSENTIALLY DIAGRAMMATIC AND ALTHOUGH THE SIZE AND LOCATIONS (2) FOR INDOOR FINAL CONNECTION TO HVAC EQUIPMENT. LENGTH SHALL NOT EXCEED 36".
<br /> OF EQUIPMENT ARE SHOWN TO SCALE WHEREVER POSSIBLE, CONTRACTOR SHALL MAKE USE OF ALL DATA 1. INSTALL ENGRAVED NAMEPLATES FOR EACH PANELBOARD, CABINET, DISCONNECT, ETC.
<br /> IN ALL CONTRACT DOCUMENTS AND VERIFY THIS INFORMATION AT THE SITE. CONTRACTOR SHALL BE E. "PVC" SCHEDULE 40: NAMEPLATES SHALL BE SECURELY FASTENED TO THE EQUIPMENT WITH #4 PHILLIPS ROUND HEAD
<br /> RESPONSIBLE FOR LAYING OUT AND INSTALLING HIS WORK TO AVOID INTERFERENCE WITH OTHER TRADES. (1) FOR CONDUITS RUN UNDERGROUND AND FOR UNDER BUILDING SLAB. CADMIUM PLATED SELF-TAPPING SCREWS, BRASS BOLT.
<br /> (2) CONDUIT STUBUPS THROUGH THE FLOOR OR GRADE SHALL BE IN PVC WRAPPED RIGID STEEL
<br /> 7. WORK SHOWN ON THE DRAWINGS TO BE INSTALLED UNDERGROUND SHALL BE INSTALLED AT LEAST 24" CONDUIT. PVC WRAPPING SHALL EXTEND 6"ABOVE FINISHED FLOOR OR GRADE. 2. PROVIDE CIRCUIT LABEL INDICATING PANEL AND CIRCUIT NUMBER ON EACH COVERPLATE FOR
<br /> BELOW GRADE UNLESS OTHERWISE NOTED. BACKFILL IN 6"THICK, PROPERLY MOISTENED LAYERS, (3) NOT PERMITTED FOR WIRING ABOVE FINISHED FLOOR INSIDE BUILDINGS EACH RECEPTACLE AND LIGHT SWITCH, MOTION SENSOR SWITCH. SUCH LABEL SHALL BE SELF ADHESIVE
<br /> SOLIDLY PACKED AND IRON TAMPED TO A DENSITY NOT LESS THAN THAT OF ADJACENT, UNDISTURBED WHITE TAPE WITH BLACK LETTERS MADE ON A LABEL MAKER.
<br /> EARTH. RESTORE SURFACES, ROADWAYS, WALKS, CURBS, WALLS AND EXISTING UNDERGROUND F. ALUMINUM CONDUITS, IMC CONDUITS OR ALUMINUM FITTINGS ARE NOT APPROVED FOR USE ON
<br /> INSTALLATIONS TO ORIGINAL CONDITION IN AN ACCEPTABLE MANNER. THIS PROJECT. 3. ALL CONTROLLED RECEPTACLES SHALL BE PERMANENTLY MARKED TO DIFFERENTIATE THEM
<br /> FROM UNCONTROLLED RECEPTACLES PER CALIFORNIA ENERGY CODE SECTION 130.5(d)(3).
<br /> 8. ALL ELECTRICAL EQUIPMENT EXPOSED TO THE WEATHER SHALL BE LISTED FOR EXTERIOR USE. G. ALL CONDUIT FITTINGS SHALL BE MALLEABLE IRON/STEEL.
<br /> 262726. WIRING DEVICES:
<br /> 9. ALL U.L. LISTED EQUIPMENT SHALL BE INSTALLED AS PER THEIR LISTING OR LABELING. H. COUPLING:
<br /> (1) EMT COUPLING -APPLETON TWC-CS SERIES 1. UNITS SHALL BE EQUAL TO THE DEVICES SET FORTH HEREIN, IN STANDARD COLORS (BROWN, Client:
<br /> 10. IN LOCATIONS WHERE ELECTRICAL EQUIPMENT WOULD BE EXPOSED TO PHYSICAL DAMAGE, (2) EMT CONNECTOR-APPLETON TW-CSI SERIES WHITE, GREY, BEIGE OR IVORY)AS SELECTED BY THE ARCHITECT: ORLANDO'S
<br /> ENCLOSURES OR GUARDS SHALL BE SO ARRANGED AND OF SUCH STRENGTH AS TO PREVENT SUCH (3) FLEX CONDUIT CONNECTOR-T&B "TITE BITE", INSULATED A. WIRING DEVICES LEVITON # HUBBELL# P & S#
<br /> DAMAGE. (4) LIQUID TIGHT FLEX CONDUIT CONNECTOR-APPLETON "STB" SERIES UP TO 2", "ST" SERIES OVER 2". SINGLE POLE SWITCH, 15A 1201-2 HBL1201 PS15AC1
<br /> DOUBLE POLE SWITCH, 15A 1202-2 HBL1202 PS15AC2 18754 E Highway 26
<br /> 11. CONFLICTS BETWEEN SPECIFICATIONS AND PLANS: I. RIGID STEEL CONDUIT CONNECTED TO BOXES AND CABINETS SHALL BE FITTED WITH TWO THREE WAY SWITCH, 15A 1203-2 HBL1203 PS15AC3 LINDEN, CA
<br /> LOCKNUTS AND INSULATING BUSHING, OA"A" SERIES. PROVIDE GROUNDING BUSHING OZ "BL" SERIES DUPLEX CONV. OUTLET, 15A 5262 HBL5262 5262
<br /> a. ANY CONFLICT BETWEEN ELECTRICAL SPECIFICATIONS AND ELECTRICAL PLANS; OR BETWEEN WHERE LOCKNUTS AND BUSHING IS NOT USED. CONDUITS CONNECTED TO BOXES EXPOSED TO DUPLEX CONV. OUTLET, 20A 5362 HBL5362 5362
<br /> ELECTRICAL PLANS AND PLANS OF ANOTHER DISCIPLINE SHALL BE BROUGHT TO THE ATTENTION OF THE WEATHER/MOISTURE SHALL BE FITTED WITH WATERTIGHT SEALING HUBS OF STEEL OR MALLEABLE DUPLEX CONV. GFI OUTLET, 15A 6599 GF15 1595L
<br /> ENGINEER AND A RESOLUTION RECEIVED PRIOR TO PROCUREMENT OR INSTALLATION OF THE ITEM IN IRON WITH SEALING RING AND INSULATED THREAT, T& B 370 SERIES. DUPLEX CONV. GFI OUTLET, 20A 6899 GF15 2095L
<br /> QUESTION.
<br /> J. TYPE NM AND NMC CABLES SHALL NOT BE USED ON THIS PROJECT. 2. THE CONTROLLED OUTLET SHALL HAVE PERMANENT UNIQUE MARKING PROVIDED BY THE
<br /> b. IF THE CONTRACTOR PROCEEDS WITH THE WORK WITHOUT RECEIVING ANY RESOLUTION TO THE MANUFACTURER OF THE RECEPTACLE.
<br /> CONFLICT HE/SHE DOES SO AT HIS/HER OWN RISK AND SHALL RECTIFY THE WORK TO THE SATISFACTION K. THE PROJECT DRAWINGS ARE LAID OUT USING SOLID CONDUITS AND CABLES PULLED THROUGH
<br /> OF THE ENGINEER AT NO ADDITIONAL COST TO THE OWNER OR ENGINEER. SUCH CONDUITS. MC CABLES MAY BE UTILIZED AS DESCRIBED BELOW, WITH RESTRICTIONS NOTED. 3. THE MOUNTING HEIGHTS OF LIGHT SWITCHES, RECEPTACLES AND CONTROLS SHALL BE MAXIMUM
<br /> 48" MEASURED TO THE TOP OF BOXES OR MINIMUM 16"TO THE BOTTOM OF BOXES. SEE "LEGEND" FOR
<br /> 260500.02. SUBMITALLS: (1) PRIOR APPROVAL OF OWNER/ARCHITECT OR ENGINEER REQUIRED. ACTUAL MOUNTING HEIGHTS OF DEVICES. VERIFY HEIGHT WITH ARCHITECT WHERE AN ACTUAL
<br /> 1. PROVIDE THE FOLOWING SUBMITTALS FOR REVIEW AND APPROVAL. EACH SHALL BE SUBMITTED (2) MC CABLES SHALL BE AS MANUFACTURED BY SOUTHWIRE TYPE EZ-MC DURACLAD TYPE WITH LIGHT MOUNTING HEIGHT IS NOT CALLED OUT ON PLANS. Project:
<br /> SEPARATELY TO AVOID DELAYS IN THE REVIEW OF ONE SUBMITTAL IN HOLDING UP REVIEW OF THE WEIGHT STEEL ARMOR AND INSULATED GREEN GROUNDING CONDUCTORS OR APPROVED EQUAL. 4. SINGLE RECEPTACLE SERVED BY INDIVIDUAL 20A BRANCH CIRCUIT DEDICATED TO THE OUTLET BAR REMODEL
<br /> REMAINDER. SHALL BE 20A RATED PER CEC 210.21(13)(1). ALL OTHERS SHALL BE 15A RATED.
<br /> (3) SHALL BE USED FOR BRANCH CIRCUITS ONLY AS NOTED BELOW.
<br /> d. LIGHTING CONTROL PANEL. 5. ALL 15A AND 20A, 120V OUTLETS IN KITCHEN SHALL BE GFCI PER CEC 210.8(B)(2). LOCATE SUCH
<br /> e. LIGHTING CONTROLS (a) CANNOT BE USED ANYWHERE EXPOSED. OUTLETS SO THAT THEY ARE ACCESSIBLE AFTER APPLIANCES THAT ARE PLUGGED INTO THE OUTLETS 18754 E Highway 26
<br /> b. PANEL BOARDS ARE IN PLACE. LINDEN, CA
<br /> f. BASIC ELECTRICAL MATERIALS (b) LIGHTING: VERTICAL DROPS IN WALL FOR LIGHT SWITCHES FORM JBOX IN CEILING. HORIZONTAL
<br /> C. LIGHT FIXTURES RUNS IN CEILING SHALL BE IN SOLID STEEL CONDUITS. 6. ALL RECEPTACLES INSTALLED OUTDOORS SHALL BE WEATHERPROOF AND HAVE GROUND FAULT
<br /> CIRCUIT INTERRUPTER PROTECTION.
<br /> 260526. GROUNDING: (c) POWER RECEPTACLES:
<br /> 262726.02. DEVICE PLATES:
<br /> 1. GROUND AND BOND ALL EQUIPMENT AS REQUIRED BY GOVERNING CODES AND SPECIFICALLY (1) FOR UNDERGROUND HOMERUNS: SOLID CONDUIT VERTICAL RISER IN WALL FROM UNDERGROUND
<br /> INCLUDING SWITCHBOARD, PANELBOARDS, MOTOR CASES, METAL PIPING SYSTEMS, STRUCTURAL STEEL, CONDUIT TO FIRST RECEPTACLE JBOX. THEN HORIZONTAL RUNS WITHIN WALLS TO OTHER 1. ALL DEVICE PLATES FOR INDOOR USE SHALL BE NYLON.
<br /> ETC. RECEPTACLE BOXES IN MC CABLE.
<br /> (2) FOR OVERHEAD HOMERUNS: VERTICAL DROPS FROM JBOX IN CEILING THEN HORIZONTAL RUNS 2. ALL DEVICE BOXES WHICH ARE INSTALLED IN FIRE RATED WALL ASSEMBLY AND IS PROVIDED WITH
<br /> 2. PROVIDE GROUND WIRES IN ALL FEEDERS AND BRANCH CIRCUITS, SIZE PER CEC TABLE 250.122 WITHIN WALLS TO OTHER RECEPTACLES. HORIZONTAL RUNS IN CEILING SHALL BE IN SOLID STEEL A FIRE-STOPPING PUTTY PAD SHALL HAVE A BRUSHED STAINLESS STEEL COVERPLATE IN ACCORDANCE
<br /> CONDUITS. WITH THE REQUIREMENTS OF THE PUTTY PAD.
<br /> 3. ALL GROUND WIRES SHALL BE INSULATED GROUND WIRES.
<br /> (d) NO OTHER USE IS PERMITTED WITHOUT SPECIFIC WRITTEN APPROVAL OF THE ARCHITECT OR 3. DEVICE COVERS FOR SURFACE MOUNTED BOXES SHALL BE 1/2" RAISED STEEL PLATES.
<br /> ENGINEER.
<br /> 260529. INSTALLATION OF SUPPORT SYSTEMS 4. DEVICE COVERS FOR DEVICES LOCATED IN DAMP LOCATIONS SHALL COMPLY WITH CEC 406.9(A).
<br /> (4) ALL FITTINGS AND TERMINATIONS FOR THE MC CABLING SYSTEM SHALL BE METAL AND SUITABLE
<br /> 1. RACEWAYS, CABLE ASSEMBLIES, BOXES, CABINETS, AND FITTINGS SHALL BE SECURELY FASTENED AND LISTED FOR SUCH USE. 5. DEVICE COVERS FOR DEVICES LOCATED IN WET LOCATIONS SHALL COMPLY WITH CEC 406.9(B).
<br /> IN PLACE PER CEC ARTICLE 300.11. SUPPORT WIRES THAT DO NOT PROVIDE SECURE SUPPORT SHALL NOT
<br /> BE PERMITTED AS THE SOLE SUPPORT. SUPPORT WIRES AND ASSOCIATED FITTINGS THAT PROVIDE (5) ALL SUPPORTS, ATTACHMENTS SPACING SHALL BE PER CEC 330.30.
<br /> SECURE SUPPORT AND THAT ARE INSTALLED IN ADDITION TO THE CEILING GRID SUPPORT WIRES SHALL BE 265100. LIGHTING:
<br /> PERMITTED AS THE SOLE SUPPORT. WHERE INDEPENDENT SUPPORT WIRE ARE USED, THEY SHALL BE (6) FOR MULTI-WIRE BRANCH CIRCUITS SUCH CABLES SHALL HAVE MULTIPLE NEUTRALS, ONE FOR
<br /> SECURED AT BOTH ENDS. CABLES AND RACEWAYS SHALL NOT BE SUPPORTED BY CEILING GRIDS. EACH CIRCUIT. 1. ALL LUMINAIRES SHALL BE CERTIFIED BY THE MANUFACTURER TO THE CALIFORNIA ENERGY
<br /> COMMISSION:
<br /> 2. FURNISH ALL NECESSARY FOUNDATIONS, SUPPORTS, BACKING, ETC., FOR ALL ELECTRICAL 6. CONDUCTORS SHALL BE COPPER CONDUCTORS TYPE THHN/THWN UNLESS OTHERWISE NOTED
<br /> ENCLOSURES, CONDUITS AND EQUIPMENT. OR REQUIRED BY CODE. A. ALL LUMINAIRES SPECIFIED ON THIS PROJECT SHALL BE AS NOTED IN THE "LIGHT FIXTURE
<br /> SCHEDULE" ON THESE PLANS. NO SUBSTITUTES ARE PERMITTED WITHOUT WRITTEN APPROVAL OF THE
<br /> 3. ATTACH ALL BOXES, CABINETS, ETC. TO WOOD WITH WOOD OR LAG SCREWS, TO METAL WITH 7. ALL DEVICES, CONDUITS, RACEWAYS AND CABLES SHOWN ARE NEW TO BE PROVIDED UNLESS ENGINEER.
<br /> MACHINE SCREWS OR BOLTS AND TO CONCRETE WITH EXPANSION ANCHORS AND MACHINE SCREWS OR OTHERWISE NOTED.
<br /> BOLTS. B. ALL INTERIOR LUMINAIRES SHALL BE PROVIDES WITH 0-10V DIMMING LED DRIVERS.
<br /> 8. FLASH AND COUNTERFLASH ALL ITEMS PASSING THROUGH THE ROOF.
<br /> 2. RIGID STEEL CONDUIT SHALL BE SUPPORTED AT INTERVALS NOT GREATER THAN 10 FT, ELECTRICAL 9. THE OWNER RESERVES THE RIGHT TO RELOCATE ALL LIGHTING, OUTLETS AND SWITCHES C. ALL EXTERIOR LUMINAIRES SHALL BE PROVIDED WITH 0-10V DIMMING LED DRIVERS WITH
<br /> METALLIC TUBING AT INTERVALS NOT GREATER THAN 5 FT. BEFORE THEY ARE ROUGHED IN AT NO EXTRA COST. INTEGRAL MOTION SENSORS WHERE SO NOTED.
<br /> 3. A SUPPORT SHALL BE PROVIDED NOT MORE THAN 3 FT. FROM ANY CHANGE IN DIRECTION. 10. SEPARATION OF WIRING OF DIFFERENT VOLTAGE CLASSIFICATIONS: 265300. EXIT AND MEANS OF EGRESS EMERGENCY LIGHTING: Project No.: 2017.xxx
<br /> ADDITIONAL SUPPORTS TO THOSE SPECIFIED ABOVE SHALL BE INSTALLED WHERE REQUIRED TO SUIT JOB
<br /> CONDITIONS AND TO PROVIDE A SECURE INSTALLATION. ALL HANGERS AND SUPPORTS SHALL BE THE A. WIRING FOR DIFFERENT VOLTAGE CLASSIFICATIONS SHALL BE INSTALLED IN ENTIRELY 1. PROVIDE EXIT SIGNS IN ACCORDANCE WITH CBC SECTION 1011.1. PROVIDE MEANS OF EGRESS Drawn By: RCS
<br /> PRODUCTS OF ONE MANUFACTURER. SEPARATE RACEWAYS/CONDUITS SYSTEM AND ENCLOSURES/BOXES. ILLUMINATION IN ACCORDANCE WITH CBC SECTION 1006. PROVIDE FLOOR-LEVEL EXIT SIGNS PER CBC
<br /> 1011.7 IF REQUIRED Checked By: RCS
<br /> 260519.01. SEISMIC BRACING FOR SUSPENDED FIXURES: CLASSIFICATION 1 -0 TO 30V
<br /> CLASSIFICATION 2 - 100 TO 250V 2. ELECTRICAL CONTRACTOR SHALL RE-VERIFY PLACEMENT OF ALL EXIT SIGNS AS TO ENSURE THAT
<br /> 1. ALL SUSPENDED FIXTURES SHALL BE ABLE TO SWING AND SWAY 45° IN ANY DIRECTION WITHOUT CLASSIFICATION 3 -251 TO 500V THEY ARE CLEARLY VISIBLE FROM ANY DIRECTION OF APPROACH WITHIN THE PATH OF EXIT TRAVEL TO No. Description Date By
<br /> HITTING AN OBSTRUCTION SUCH AS DUCT, PIPE, BEAM, ETC. AND WITHIN EXITS INSIDE THE BUILDING. THIS VERIFICATION SHALL BE CARRIED OUT AT ROUGHIN STAGE.
<br /> B. PARTICULAR ATTENTION SHALL BE PAID TO THE WIRING FOR THEY SHALL BE LOCATED AS NECESSARY TO CLEARLY INDICATE THE DIRECTION OF EGRESS TRAVEL. NO
<br /> 2. IF NOT, PROVIDE SEISMIC RESTRAINT PER CBC AND AS REQUIRED, USING #10 GA WIRES WITH POINT IN THE EXIT PATH SHALL BE MORE THAN 100 FT. FROM THE NEAREST VISIBLE SIGN. ALL IN
<br /> MINIMUM (3)TWISTS AROUND THE TIE AT EACH END U.O.N. SPECIFICALLY. 1. ROOF TOP CONVENIENCE OUTLETS FOR SERVICING ROOF TOP EQUIPMENT. ACCORDANCE WITH CBC SECTION 1011.1. RELOCATE AND/OR ADD EXIT SIGNS AS NECESSARY TO ACHIEVE
<br /> THIS. PROVIDE PENDANTS TO MOUNT SIGNS AS NECESSARY TO ACHIEVE THIS.
<br /> 3. FOR A LINEAR FIXTURE THIS TYPICALLY MEANS TWO BRACES AT 45° TO THE HORIZONTAL AND 90° 2. LINE VOLTAGE CONTROLS FOR ROOF TOP HVAC AND OTHER REQUIREMENTS.
<br /> BETWEEN THE BRACES AT EACH END, FOR A TOTAL OF (4) BRACE WIRES. 3. THE FINAL NUMBER AND LOCATION OF EXIT SIGNS SHALL BE DETERMINED IN THE FIELD BY THE
<br /> C. DISCONNECTS SHALL NOT BE USED AS THROUGH RACEWAYS FOR WIRING NOT DIRECTLY FIRE MARSHALL AND BUILDING INSPECTOR.
<br /> 260533. PULL OR JUNCTION BOXES: SERVING THE DISCONNECTS. SERVICING OUTLETS SHALL NOT BE MOUNTED ON DISCONNECTS.
<br /> 4. INDIVIDUAL UNIT EQUIPMENT FOR EMERGENCY ILLUMINATION SHALL COMPLY WITH CEC SECTION
<br /> 1. INSTALL WHERE INDICATED, OR AS REQUIRED BY CODE, PULL BOXES AND JUNCTION BOXES OF 260551. INSTALLATION OF RACEWAYS AND FITTINGS 700.12(F). THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE THE SAME BRANCH CIRCUIT AS
<br /> SUFFICIENT SIZE AND CAPACITY TO FACILITATE ALL WIRING. BOXES SHALL BE SIZED TO PROPERLY THAT SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL SWITCHES.
<br /> ACCOMMODATE ALL CONDUCTORS ENTERING SAME. 1. CONCEAL RACEWAYS WITHIN CEILINGS, WALLS, AND FLOORS EXCEPT WHERE EXPOSED
<br /> RACEWAYS ARE SPECIFICALLY PERMITTED. 5. ALL EMERGENCY LIGHTS AND EXIT SIGNS SHALL BE PROVIDED WITH AN UNSWITCHED HOT WIRE.
<br /> 2. BOXES SHALL BE OF THE SHAPE AND SIZE BEST SUITED FOR THE PARTICULAR APPLICATION AND
<br /> SHALL BE SUPPORTED DIRECTLY TO STRUCTURAL MEMBERS, FRAMING OR BLOCKING BY MEANS OF 6. ALL EMERGENCY LIGHT FIXTURES WITH INTEGRAL BATTERY BALLASTS SHALL BE SWITCHED AS
<br /> SCREWS, ANCHORS, BOLTS OR EMBEDDED IN MASONRY. 2. WHERE CONDUIT IS ALLOWED TO BE EXPOSED, INSTALL THE CONDUIT PARALLEL WITH OR AT SHOWN AND SHALL COME ON IN EMERGENCY POWER-OFF MODE UPON POWER FAILURE. TO THIS EFFECT
<br /> RIGHT ANGLES TO STRUCTURAL MEMBERS, WALLS, AND LINES OF THE BUILDING. PROVIDE AN UNSWITCHED POWER WIRE TO EACH SUCH FIXTURE FROM THE SAME CIRCUIT AS THAT
<br /> w A. SWITCH AND RECEPTACLE BOX SHALL BE ONE PIECE DRAWN OR STAMPED STEEL BOXES MINIMUM FEEDING THE LIGHT FIXTURE. PERMIT SUBMITTAL
<br /> SIZE SHALL BE FOUR INCHES (4") SQARE. BOXES SHALL BE FITTED WITH FLUSH DEVICE COVERS, PLASTER 3. INSTALL WHERE INDICATED, OR AS REQUIRED BY CODE, PULLBOXES AND JUNCTION BOXES OF $-6-ZO1 H
<br /> RINGS, OR TILE SWITCH RINGS IN MASONRY IN AREA WHERE EXPOSED WIRING IS PERMISSIBLE, BOXES SUFFICIENT SIZE TO FACILITATE WIRING. BOXES SHALL BE SIZED TO PROPERLY ACCOMMODATE ALL
<br /> SHALL BEFITTED WITH SURFACE TYPE COVERS. CONDUCTORS ENTERING SAME.
<br /> 0
<br /> B. LIGHTING OUTLETS SHALL BE FOUR INCHES (4")OCTAGON, MINIMUM. 4. DO NOT INSTALL CONDUIT OR TUBING WHICH HAS BEEN CRUSHED OR DEFORMED.
<br /> D. WEATHERPROOF BOXES SHALL BE APPLETON FD SERIES AND FITTED WITH GASKETED CAST 5. RUN CONDUCTORS OF SAME CIRCUIT IN SAME CONDUIT. RUN CONDUCTORS OF DIFFERENT GENERAL NOTES
<br /> COVERS. VOLTAGE SYSTEMS IN SEPARATE CONDUITS.
<br /> 0
<br /> 0
<br /> E. VOICE/DATA OUTLET BOXES SHALL BE 4_11/16"SQ.x2_1/8" DEEP MINIMUM, FITTED WITH PLASTER 6. INSTALL NO CONDUCTORS UNTIL WORK WHICH MIGHT CAUSE DAMAGE TO SUCH CONDUCTORS
<br /> RINGS. OR THE CONDUIT HAS BEEN COMPLETED. QRoFESSipN
<br /> C. S ��F
<br /> F. BOXES FOR SPECIAL EQUIPMENT SHALL BE SUITABLE FOR THE PARTICULAR EQUIPMENT. 7. KEEP ALL CONDUITS AT LEAST SIX INCHES AWAY FROM THE COVERING ON HOT WATER OR H C S ENGINEERING INC.
<br /> STEAM PIPES. 430
<br /> G. BOXES SHALL BE LOCATED AND PLACED ACCORDING TO ARCHITECTURAL AND STRUCTURAL No. E1
<br /> REQUIREMENTS. 8. CAP RACEWAY ENDS DURING CONSTRUCTION. CLEAN OR REPLACE CONDUITS IN WHICH WATER * Exp. 6-330-0-11