Laserfiche WebLink
SAN10 A Q U I N Environmental Health Department <br /> C 0 (J t% 1 I Y _ <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date : <br /> ER Vine Stockton 4733 S HWY 99 , STOCKTON June 28 , 2019 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I, CLASS II , or MINOR - Notice to Comply) <br /> Item # Remarks <br /> 103 HSC 25292 . 2 , 25299 . 30 Failure to submit and maintain complete and current financial responsibility documents. <br /> Financial responsibility documents have not been submitted to the EHD . The financial responsibility documents on <br /> CERS are dated 01 /01 /2018 . Current financial responsibility documents are required to be submitted annually . <br /> Immediately log into the California Environmental Reporting System ( CERS) at http : //cers , calepa . ca . gov/, and upload <br /> the required documents . <br /> This is a minor violation. <br /> 106 CCR 2632 (d ) (2 ) , 2634 (e) Failed to have an approved UST response plan . <br /> The response plan is not current on CERS . The response plan on site is dated 01 /23/2019 , while the one on CERS is <br /> dated 08/ 14/2014 . The current response plan must be uploaded to the California Environmental Reporting System <br /> (CERS) . Immediately log into CERS , upload the completed form , and submit for review by the EHD . Ensure a copy <br /> is available for inspection at any time . <br /> This is a minor violation. <br /> 201 CCR 2712 (b ) ( 1 -2 ) Failure to maintain monitoring , maintenance , and follow up action records . <br /> Maintenance and monitoring records for the last three years were not found on site . <br /> -Secondary containment testing results performed on 10/25/2018 were not found on site . <br /> These records shall be maintained on site for at least three years . Monitoring records include : ( 1 ) date and time of all <br /> monitoring or sampling ; (2 ) monitoring equipment calibration and maintenance records ; (3) results of any visual <br /> observations ; (4) results of sample analysis performed a lab or in the field ; (5) logs of all readings of gauges or other <br /> monitoring equipment , ground water elevations , or other test results ; (6 ) results of inventory readings and <br /> reconciliations . Immediately locate and maintain all maintenance and monitoring records for the last three years on <br /> site and submit copies to the EHD <br /> This is a minor violation. <br /> 209 CCR 2716 (a-e) Failure to conduct the designated UST operator visual inspection at least once every 30 days . <br /> The designated operator failed to check and note all required items on the visual inspection reports . <br /> -The designated operator visual inspection reports of 3/6/19 , 2/6/19 , 1 /9/19 , 12 /12/18 , 11 /12/ 18 , and 10/17/18 state <br /> that the secondary containment testing was performed on 10/22/18 instead of 10/25/18 <br /> -The designated operator visual inspection reports of 5/31 /19 state that the secondary containment testing was <br /> performed on 10/13/19 instead of 10/25/18 <br /> -The 10/17 /18 inspection reports left blank section V . <br /> During the visual inspection , the designated operator shall check that all required testing and maintenance for the <br /> UST system have been completed and shall check all required items on the report . Ensure that designated operators <br /> performing visual inspections at this facility are including all of the required information on the reports . <br /> This is a minor violation. <br /> FA0003924 PR0232510 SCO01 06/28/2019 <br /> EHD 23-01 Rev. 09/28/2018 Page 4 of 6 Underground Storage Tank Program OR <br /> 1868 E . Hazelton Avenue Stockton , California 95205 1 T 209 468 -3420 F 209 464 -0138 1 www. sjcehd . com <br />