Laserfiche WebLink
SAN J O A R N Environmental Health Department <br /> i , �V <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> CANEPAS CAR WASH STORE 642 N HUNTER ST, STOCKTON October 30, 2019 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 306 CCR 2630(d), 2641(a) Monitoring equipment is not installed or maintained to detect a leak at the earliest <br /> opportunity. <br /> The sensors in UDC 6/8 and 2/4 were tilted at about 45 degrees and not located to detect a leak at the earliest <br /> opportunity. Monitoring equipment shall be maintained to be able to detect a leak at the earliest possible opportunity. <br /> Immediately relocate this sensor to the lowest point. <br /> This is a Class II violation. <br /> 313 HSC 25290.1,25290.2, 25291 Failure to construct, operate, and maintain primary containment as product-tight. <br /> A small amount of oily liquid was found in the UDC 9/11 sump, indicating a leak in the primary piping.All primary <br /> containment for the UST system must be tight. Immediately have a properly licensed, trained, and certified <br /> contractor repair or replace the failed component under permit and inspection of the EHD. <br /> This is a minor violation. <br /> Overall Inspection Comments: <br /> NOTE: On site to witness monitoring system certification. Paperwork inspection was conducted on June 27, <br /> 2019. All violations from that day were required to be followed up by July 26, 2019. While EHD was onsite, EHD <br /> was informed that Hussein Alzghoul is no longer the owner and Moe Alzghoul or Moe Hamdi are no longer the <br /> operator. Store manager, Sonia Salazar stated that new owner Abdo Ashir has been operating since August 16, <br /> 2019. When I spoked to Abdo Ashir on the phone, he stated that he is familiar with the change of ownership <br /> process and that he will be coming in soon. He stated escrow has been not finalized yet. <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, by 11/29/2019. <br /> Starting September 1, 2018, all in-office CERS help will be provided at EHD hourly rate ($152). To schedule an <br /> appointment, please call (209)468-3420. <br /> Documents provided during inspection: <br /> -Return to compliance certification <br /> -Corrective Action Statement <br /> -EHD class schedule <br /> AFTER THE COMPLIANCE DATE, EHD WILL BILL FOR ALL TIME AND ACTIVITIES ASSOCIATED WITH BRINGING <br /> THIS FACILITY BACK INTO COMPLIANCE. <br /> THIS FACILITY IS SUBJECT TO REINSPECTION AT ANY TIME AT EHD'S CURRENT HOURLY RATE. <br /> Received by: Date: October 30, 2019 Inspector: Inspector Phone: <br /> Printed Name and Title: SHEWIT WOLDEAREGAY, EH Specialist (209)468-0216 <br /> Sonia Salazar, manger <br /> FA0000799 PR0231148 SC333 10/30/2019 <br /> EHD 23-01 Rev.9/20/2019 Page 4 of 4 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />