Laserfiche WebLink
SANJ O A Q U I N Environmental Health Department <br /> COUNTY <br /> b . In the dispenser sump crossover piping detail for FRP states a 2 " single wall vapor <br /> recovery piping exiting the under dispenser containment . Vapor recovery single wall <br /> cannot be installed . Revise and resubmit . <br /> 10 ) M . 5 . 3 . 12 — in the Ltank sump drain port detail , indicate how the brine communication will be <br /> tested . Revise and resubmit . <br /> 11 ) G . 5 . 3 . 23- In the D . D : side view section diagram , indicate test port depiction for vacuum <br /> communication . Revise and resubmit . <br /> 12 ) G . 5 . 3 . 25 - In the D . D : side view section diagram , indicate test port depiction for vacuum <br /> communication . Revise and resubmit . <br /> If you have any further questions , please contact me at ( 209 ) 46 &3455 . <br /> Thank ou , <br /> Betty o , *HS <br /> Environmental Health Specialist <br /> Cc: attn: David F. Allen, BP West Coast, LLC, 4 Centerpointe Drive, La Palma, CA . 90623 <br /> 2of2 <br />