Laserfiche WebLink
Spill Bucket 'Testing Deport <br /> 1 . FACILITY INFORMATION <br /> Facility Name : Pershing Holdings Inc . Date of Testing : 2/ 19/2Q19 <br /> Facility Address : 1329 Escalon Ave. Escalon , CA 95320 <br /> Facility Contact : Sunny Phone : (209) 992- 1255 <br /> 2 . TESTING CONTRACTOR INFORMATION <br /> Company Name : Diamond Petroleum Services, Inc , <br /> Technician Conducting Test . Guadalupe Sanchez <br /> Contractor License # 1005444 ICC Certification # 5250451 <br /> 3 . SPILL BUCKET TESTING INFORMATION <br /> Test Method Used : Hydrostatic <br /> Test Equipment Used : Standard Tape Measure Equipment Resolution : 1 / 16" <br /> Identify Spill Bucket (By Tank T1 : 87 South Fill TI : 87 North Fill T2 : 91 Fill <br /> Number, Stored Product, etc.) <br /> Bucket Installation Type : Direct Bury Direct Buy Direct Bury Direct Bury <br /> x Contained in Sump x Contained in Sunip x Contained in Sunip Contained in Sum <br /> Bucket Inside Diameter: 11 " 11 " 11 " <br /> Bucket Depth : 13 '/," 13 1 /8 " 14 1 /8 " <br /> Wait time between applying 5 minutes 5 minutes 5 minutes <br /> vacuum/water and start of test . <br /> Test Start Time (Ti) : 10 :45 a. m . 10 : 50 a. m . 10 : 55 a. m . <br /> Initial Reading (Ri) : 12 %z" 12 '/z" 13 1 /8" <br /> Test End Time (TF) : 11 :45 a . m . 11 : 50 a. m. 11 : 55 a.m . <br /> Final Reading (RF) : 12 %" 12 %z" 13 1 /8" <br /> Test Duration ('17F . TI) : I hr I lir I hr <br /> Change in Reading (RF - Rj): 0 0 0 <br /> Pass/Fail Threshold or 1 /8" 1 /8 " 1 /8 " <br /> Criteria : <br /> Test Result: x Pass Fail x Pass Fail x Pass Fail Pass ❑ Fail <br /> Continents : <br /> ICU <br /> MA 201 <br /> i / G...-. A pAif i t iAl 5 q <br /> Technician ' s Signature : ,_. .� �L ate ' t j Date : 2/ 19/2019 <br />