Laserfiche WebLink
6. UNDER-DISPENSER CONTAINMENT UDC TESTING <br /> Company Name , B . Z. Service Station Maintenance <br /> Company Address: 1041 Triangle Ct., West Sacramento, CA 95605 <br /> Credentials : ® CSLB Licensed Contractor ❑ SWRCB Licensed Tank Tester <br /> License Type : ICC License Number: 433159 <br /> Test Equipment Used : INCON TS-STS Equipment Resolution : 0. 0001 <br /> UDC # 9/10 UDC # 11 / 12 UDC # UDC # <br /> UDC Manufacturer: UNK UNK <br /> UDC Material : PLASTIC PLASTIC <br /> UDC Depth : 28 " 28 " <br /> FHeight from UDC Bottom to Top 8 " 8 " <br /> i hest Pi in Penetration : <br /> ht from UDC Bottom to 10 " 10 "est Electrical Penetration : <br /> dition of UDC prior to FAIR FAIR <br /> testing: <br /> Portion of UDC Tested ' 20 " 20 " <br /> Does turbine shut down when <br /> UDC sensor detects liquid (both ® Yes ❑ No ❑ NA ® Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA <br /> product and water)?' <br /> Turbine shutdown response time 6 SEC 6 SEC <br /> Is system programmed for fail- <br /> safe shutdown?' ® Yes ❑ No ❑ NA ® Yes F1No ElNA ❑ Yes ❑ No F] NA ElYes ElNo F1NA <br /> ailf <br /> Was ail-safe verified to be <br /> o s nal? « ® Yes F] No El NA ❑ Yes El No ❑ NA F] Yes El No El NA F1 Yes El No F1 NA <br /> Wait time between applying <br /> pressure/vacuum/water and 15 MIN 15 MIN <br /> starting test <br /> Test Start Time : 12 : 24 12 : 24 <br /> Initial Reading (RI) : 0.8178 3. 1544 <br /> Test End Time : 12 : 39 12 : 39 <br /> Final Reading ( RF) : 0. 8171 3. 1540 <br /> Test Duration : 15 MIN 15 MIN 15 MIN 15 MIN <br /> Change in Reading (RF-Rj) : 0. 0007 0. 0004 <br /> Pass/Fail Threshold or Criteria : 0.002 0. 002 0. 002 0. 002 <br /> Test Result: ® Pass ❑ Fail ® ;Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Was sensor removed for testing? ® Yes ❑ No ❑ NA ® Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA <br /> Was sensor properly replaced and <br /> verified functional after laced ? ® Yes F] No E] NA ® Yes [:] No F1 NA El Yes El No El NA ❑ Yes F1 No El NA <br /> testinComments — (include information on repairs made prior to testing, and recommended follow-up for f•ailed tests) <br /> Secondary Containment Test Results 6 of 6 <br />