Laserfiche WebLink
Recommended Practices for the Testing and Verification of Spill,Overfill,leak Detection and Secondary Containment Equipment at UST Facilities <br /> interstitial space is raised and is monitored for a spec:i 4.2 Tank Secondary Containment Integrity Testing <br /> Pied period of time to determine if the containment has — Dry Test Method <br /> integrity. <br /> 4.2.1 Purpose. This method is used to test the <br /> A tank secondary containment integrity test does not integrity of the dry secondary containment of a <br /> necessarily determine whether the primary tank is tight UST <br /> because portions of the primary tank.such as tank fittings <br /> and manway openings, may not be included in the con- 4.2.2 Description of Test. A partial vacuum is <br /> U"ment integrity test. drawn on the interstitial space and it is monitored <br /> for a specified period of time.If the vacuum level is <br /> maintained,the containment system has passed the <br /> test. The vacuum test time depends on the volume <br /> of the annular space and site conditions. <br /> 4.2.3 Test Conditions. The primary tank may <br /> contain any level ut product. No bulk_ deliveries <br /> shall occur during the test. <br /> CAUTION: Use only an air-operated vacu- <br /> um source or a vacuum pump powered by <br /> an explosion-proof motor. Vacuum pumps <br /> with electric motors that are not explo- <br /> sion-proof may ignite flammable vapors. <br /> If a portable air compressor is used, it <br /> should be located at least 20 feet away <br /> from the venturi-eductor or outside any <br /> Class I. Division 1 area. <br /> FIGURE 41. A cutaway view of a double-walled tank. <br /> lumber'5 <br /> Plug <br /> Vacuum Automatic Vacuum Contrtsl 0-30'Hg <br /> Sou{ce ShuloH Valve Valve Vacuum Gauge <br /> RECEIVED <br /> y� <br /> NOV 01 2019 1 <br /> ENVIRONMENTAL HEALTH <br /> DFPARTMENT <br /> Tank <br /> FIGURE 42. Schematic of the dry test method apparatus. <br /> pei.org Q <br />