Laserfiche WebLink
. LDT 5000 Field Test Apparatus Page 1 of 1 <br /> ,j Tanknology Line Leak Detector Test <br /> Work Order: 2346947 Date : 9/23/2020 <br /> Site Name / ID : 7- ELEVEN # 17334 MKT 2368 ( N -747) / 17334 <br /> Address : 4501 N . PERSHING AVE . @ ROSEMARIE LN . <br /> City : STOCKTON State : CA Zip : 95207 <br /> Tank ID T- 1 T-2 <br /> Product RUL PUL <br /> Product Line 1 1 <br /> Tested From 3 1 <br /> Existing /New Existing Existing <br /> Mechanical/Electronic Mechanical Mechanical <br /> Manufacturer/Model Vaporless LD-2000 Vaporless LD-2000 <br /> Serial No . 19011027 15021404 <br /> Pump Operating Pressure ( psi) 30 . 00 29 . 00 <br /> Calibrated Leak (ml/min ) 189 . 0 189 . 0 <br /> Calibrated Leak (gph ) 3 . 00 3 . 00 <br /> Holding PSI 30 . 00 29 . 00 <br /> ` NIA for Electronic LD's <br /> Resiliency (ml) 220 . 00 260 . 00 <br /> ' N/A for Electronic LD's <br /> Metering PSI 18 17 <br /> ' N/A for Electronic LD's <br /> Opening Time (sec) 5 10 <br /> N/A for Electronic LD' s <br /> est Results Pass Pass <br /> Technician Comments : Had to replace leak detector on 87 reg . due to a bad LD . Was replaced with an LD-2000 and <br /> passed . <br /> Technician Name : Jesus Saldivar Certification #: 115237 <br /> Technician Signature : �`° 6 � Expire Date : 1 /27/2022 <br /> Environmental Compliance for Petroleum Systems <br /> © 2020 Tanknology Inc, Austin, TX. All rights reserved. tanknology.com <br />