Laserfiche WebLink
2.2.6. Tank Sumps <br /> 2.2.6.1. Tank sump shall be supplied by the tank manufacturer. <br /> 2.2.6.2. Tank sump components shall be constructed of fiberglass reinforced plastic.The tank sump shall be 42,48"or 54"in diameter <br /> and must mount to the secondary containment collar.Standard tank sump shall consist of an octagon shaped base(round base is <br /> optional),round body extension and enclosure top. <br /> 2.2.6.3. The octagon base shall be 24"in height and provide 19"high panels for piping entry points.The base must be capable of joining to <br /> the collar with an internal adhesive channel. <br /> 2.2.6.4. A 34"or 40"watertight lid shall be provided by the tank manufacturer. <br /> 2.2.6.5. Refer to tank sump drawings for standard models and configurations. <br /> 2.2.7. Ladders <br /> 2.2.7.1. Ladders shall be supplied by the tank manufacturer(carbon steel,stainless steel,aluminum). <br /> 2.2.8. Anchor Straps <br /> 2.2.8.1. Straps shall be supplied by the tank manufacturer. <br /> 2.2.8.2. Number and location of straps shall be as specified by manufacturer. <br /> 2.2.8.3. Each strap shall be capable of withstanding a maximum load of 25,000 lbs. <br /> 2.2.9. Prefabricated Concrete Deadmen Anchors <br /> 2.2.9.1. Design Conditions—Deadmen shall meet the following design criteria: <br /> • Deadman shall be designed to ACI 318 <br /> • Manufactured with 4,000 psig concrete <br /> • Manufactured in various lengths <br /> • Provide adjustable anchor points for hold down straps <br /> 2.2.10.Liquid Sensor Drawstring <br /> 2.2.10.1. Galvanized steel drawstring shall be factory installed at the monitoring fitting to facilitate field insertion of sensor. <br /> 2.2.11.Fittings Threaded NPT <br /> 2.2.11.1. All threaded fittings shall be located on a manway cover or within 12"of the tank top center line.Fittings to be supplied with <br /> temporary thread protectors or threaded plugs. <br /> 2.2.11.2. All standard fittings shall be 4"diameter NPT half couplings. <br /> 2.2.11.3. Internal piping shall be terminated at least 4"from the tank bottom(6"for 12'diameter tanks). <br /> 3. EXECUTION <br /> 3.1. Installation and Testing <br /> 3.1.1. Fiberglass underground tanks must be tested and installed according to the current installation instructions provided with.the tank <br /> (refer to Containment Solutions Pub.No.INST 6001).Tanks are installed with pea gravel or crushed stone as specified in current <br /> installation instructions.Containment Solutions tanks may only be used for storing products listed in the current limited warranty. <br /> 4. LIMITED WARRANTY <br /> 4.1. Limited Warranty <br /> 4.1.1. Warranty shall be Containment Solutions limited warranty in effect at time of delivery. <br /> Copyright®Containment Solutions,Inc.•All Rights Reserved•September 2017•Pub.No.TNK 1092E <br /> 3 <br />