Laserfiche WebLink
SHAUN Environmental Health Department <br /> --C O 4) NTY Time In: <br /> ri <br /> Time Out: <br /> k , :"SS grows he"!, <br /> Underground Storage Tank Program Service Request Inspection Report <br /> Name of Facility: MANTECA LIQUOR& FOOD Date: 08/01/2019 <br /> Address: 890 N MAIN ST , MANTECA 95336 <br /> Requestor: MEGAN MITCHELL, ELITE IV CONTRACTORS Telephone: (209)461-6337 <br /> Program Element: 2308- UST RETROFIT Request#: SR0080557 <br /> Inspection Type: 298- UST RETROFIT REPAIR INSPECTION <br /> Onsite Service Technician: Chris Adams ICC Service Tech/Installer Exp. Date: 04/19/2020 <br /> Manufacturer training: OPW,05/23/21 <br /> OVERALL INSPECTION NOTES AND COMMENTS <br /> NOTES <br /> On Site for drop tube verification for 87 tank .Drop tube verified. <br /> Verified ball float removal on vent riser verified no existence of ball floats. <br /> Tank shut off at les than95% <br /> Actual tank capacity 12000gallons (95.250 inches) <br /> 95%= 11400gallons( 85.875inches) <br /> Total length of drop tube 122.75 <br /> The calculated upper drop tube length 42.875 inches (passed) <br /> Fuel can now be received in the 87 tank. <br /> The person in charge is responsible for ensuring that the above mentioned facility is in compliance with all applicable sections of the California Health and <br /> Safety Code. If a reinspection is required,fees will be assessed at the current hourly rate. <br /> Received by: Name and Title: Chris Adam, Service Tech <br /> EH Specialist: PAUL NSO Phone: (209)468-3432 <br /> FA0001393 SR0080557 SC298 08/01/2019 <br /> EHD 23-01 Rev.06/30/15 Page 1 of 1 Underground Storage Tank Program Service Request Inspection Report <br />