Laserfiche WebLink
GPH = Gallons per hour, Y = Yes, N = No, NA = Not applicable, VPH = Vacuum/Pressure/Hydrostatic, ID = Identification <br />PRESSURIZED PIPING LEAK DETECTION CERTIFICATION SHEET <br /> <br /> <br /> <br /> <br /> <br />Date: 05/22/19 CERS I.D. # 10182103 <br /> <br />Location: United Pacific #5446 Contact: Tom M. Robins <br /> 1403 County Club Blvd. <br /> Stockton, CA 95204 Telephone: (310) 323-3992 ext. #2012 <br /> <br /> <br />SUMP # #3-4 #3-4 #3-4 <br />PRODUCT T-1 Diesel T-2 87 T-3 91 <br />LD TYPE [ (M)echanical, (W)PLLD, (P)LLD ] M M M <br />LD MANUFACTURER VMI VMI VMI <br />LD MODEL LD-2000 LD-2000 LD-2000 <br />LD SERIAL NUMBER 01081406 16021590 08051079 <br />SUMP CONDITION Dry Dry Dry <br />RESILIENCY 110ml 155ml 165ml <br />OPERATING PRESSURE 30psi 28psi 28psi <br />OPENING TIME 4 seconds 5 second 4 seconds <br />METERING PRESSURE 10psi 10psi 10psi <br />FUNCTIONAL ELEMENT HOLDING PRESSURE 18psi 18psi 18psi <br />LEAK RATE LD DETECTED 3gph 3gph 3gph <br />DOES LD DETECT 3 GPH LEAK RATE? Yes Yes Yes <br />DOES VEEDER-ROOT CONSOLE ALARM? N/A N/A N/A <br />LD PASS OR FAIL? Pass Pass Pass <br /> <br />Comments: <br /> <br /> <br />Technician: Richard Thomas Contractor Lic.# 803616 <br />Signature: <br /> <br /> <br /> <br /> <br />