Laserfiche WebLink
i <br /> Recommended Practices for the Testing and Verification of Spill,Overfill,Leak Detection and Secondary Containment Equipment at UST Faciliti <br /> NOTE: If the fill cap. is not included in the the spill bucket.The vacuum level is monitored f <br /> spill bucket test and/or the cap is not tight, it a 1-minute period. <br /> could be the source of potential fuel contami- 6.3.3 Test Equipment. Test equipment sh, <br /> nation from water intrusion. include: <br /> NOTE: Before permanently plugging, ensure vacuum test apparatus (The test apparatus m. <br /> that local regulations allow the drain valve to be available from the spill bucket manufacture <br /> It includes an air pressure regulator, a vacuu <br /> be permanently plugged. <br /> -.- ,.... . _,.. source, a vacuum gauge with a minimum 0-: <br /> inch water column range and a control vale <br /> 6.2.5' Test Pr��eedure. The control valve is used to adjust the vacuu <br /> 1, Add water to the spill bucket to a level within level:); <br /> 1.5 inches of the top of the spill bucket. Allow ° test cover(The cover is equipped with a test f <br /> the water to settle for 5 minutes before the initial ting.); <br /> water level measurement is taken. <br /> ° plumber's plug(appropriate size, if used); <br /> 2.Place the measuring stick vertically at the lowest <br /> point in the spill bucket and extending above the ° stopwatch or other time-measurement devi <br /> water level to allow for an accurate measure- capable of measuring a 1-second increment; <br /> ment to be taken. The location of the measuring ° gasketing material (The purpose of the g, <br /> stick must remain the same for each water level keting material is to provide an air-tight s( <br /> measurement. Document the initial water level between the test cover and the spill bucket.). <br /> measurement as measured from the bottom of <br /> the spill bucket, Alternative measurement meth- o-50"Water Column <br /> ods may be used provided that measurement to Vacuum Vacuum Gauge <br /> 1/16(0.063) inch can be made. source <br /> 3.Take all precautions to prevent the water level <br /> from being disturbed during the duration of the control <br /> test. Valve <br /> 4. After 1 hour, document the ending water level <br /> measurement. <br /> 5. Upon completion of the test, remove and dis- <br /> pose of the water according to Section 6.7, and <br /> diy the inside of the spill bucket before returning TTank <br /> it to service. , <br /> 6.2.6 Pass/Fall Criteria. If the water level has <br /> dropped less than 1/8 (0,125)inch,the spill bucket <br /> passes the integrity test. <br /> If the water level has dropped 1/8 (0.125) inch or <br /> greater, the spill bucket fails the integrity test. <br /> 6.I Spill Bucket Integrity Testing -- Vacuum Test <br /> :FIGUFtE,6-2. The cover must make a tight seal with M <br /> M thod. spill bucket to prevent leakage when the vacuum is <br /> 6.3.1 Purpose, This method is used to test the pulled during the test. <br /> integrity of single-walled spill buckets or the pri- <br /> c.X. <br /> mary containment of secondarily contained spill t Cit Ilse Only an aircPerated vae- <br /> buckets. M <br /> uum source or a vacuum pump pow- <br /> 6.3.2 Description of Test. Using a specially eyed by an explosion-proof motor, Vacuum <br /> equipped test cover, a partial vacuum is applied to pumps with electric motors that are not <br /> i_NVIRONMENTAL HEALI H <br /> DEPAPTN/TF 1T pei.org <br />