Laserfiche WebLink
S0 JOA U 1 Environmental Health Department <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> STOCKTON AUTO CENTER CAR WASH 3434 E HAMMER LN, STOCKTON November 05, 2019 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 209 CCR 2716(a-e) Failure to conduct the designated UST operator visual inspection at least once every 30 days. <br /> 1)-A designated operator inspection was performed on 11/14/18 and the next inspection was performed on <br /> 12/18/18, 34 days later. <br /> -A designated operator inspection was due by 12/18/18 and the next inspection was performed on 1/23/19, 36 days <br /> later. <br /> -A designated operator inspection was due by 2/18/19 and the next inspection was performed on 3/15/19, 32 days <br /> later. <br /> -A designated operator inspection was performed on 3/15/19 and the next inspection was performed on 4/15/19, 31 <br /> days later. <br /> The designated operator visual inspections shall be conducted within 30 days or less of the previous inspection. <br /> Ensure that all designated operator inspections are performed within the required time frames. <br /> 2)The following was observed on the monthly inspection report: <br /> -Section VI of the report was missing the date, name, and signature of the UST owner/operator. <br /> -The designated operator documented visual inspections of all UDCs but left the question regarding UDC sensor <br /> locations blank. <br /> -The designated operator answered the question regarding sumps sensor locations but did not list which sump that <br /> was visually inspected. <br /> -Secondary containment test date was incorrectly stated as 1/14/2018 <br /> -On the 2/18/2019 monthly report date and alarm print out date do not match.Alarm print out was dated 2/15/2019. <br /> -2/18/2019 monthly report was incorrectly dated 2/18/2018. <br /> -On the 10/2/2019 monthly report date and alarm print out date do not match.Alarm print out was dated <br /> 10/30/2019. <br /> During the visual inspection,the designated operator shall check that all required testing and maintenance for the <br /> UST system have been completed and shall check all required items on the report. Ensure that designated <br /> operators performing visual inspections at this facility are including all of the required information on the reports. <br /> This is a minor violation. <br /> 306 CCR 2630(d), 2641(a) Monitoring equipment is not installed or maintained to detect a leak at the earliest <br /> opportunity. <br /> The 87 fill sump sensor was observed on its side, not at the lowest point of the sump, and not located to detect a <br /> leak at the earliest opportunity. Monitoring equipment shall be maintained to be able to detect a leak at the earliest <br /> possible opportunity. Immediately relocate this sensor to the lowest point of the 87 fill sump. <br /> This is a Class II violation. <br /> FA0003681 PR0232398 SCO01 11/05/2019 <br /> EHD 23-01 Rev.9/20/2019 Page 5 of 6 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />