e <br /> t) 1 <br /> ���I5�1°l Siwe ^rl <br /> SAN l 0 A Q U I N Environmental Health Department <br /> '7 y <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> AISLE 1 #2356 4219 E MORADA LN, STOCKTON July 09 2019 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 201 CCR 2712(b)(1-2) Failure to maintain monitoring, maintenance, and follow up action records. <br /> Maintenance and monitoring records for the last three years were not found on site. <br /> -Overfill Prevention Equipment Inspection test result <br /> -2018 Monitoring System Certification <br /> These records shall be maintained on site for at least three years. Monitoring records include: (1)date and time of <br /> all monitoring or sampling; (2)monitoring equipment calibration and maintenance records; (3)results of any visual <br /> observations; (4)results of sample analysis performed a lab or in the field; (5)logs of all readings of gauges or other <br /> monitoring equipment,ground water elevations, or other test results; (6)results of inventory readings and <br /> reconciliations. Immediately locate and maintain all maintenance and monitoring records for the last three years on <br /> site and submit copies to the EHD. <br /> This is a minor violation. <br /> 204 CCR 2712(1) Current monitoring plan approved by the EHD not found on site. <br /> An approved copy of the monitoring plans were not available for inspection. A copy of these plans shall be <br /> accessible on site at all times. Immediately locate and retain a copy on site. <br /> This is a minor violation. <br /> 205 CCR 2712(i), 2634(e) Failure to submit a current UST Response Plan and have it available onsite. <br /> An approved copy of the response plan was not available for inspection. A copy of this plan shall be accessible on <br /> site at all times. Immediately locate and retain a copy on site. <br /> This is a minor violation. <br /> 209 CCR 2716(a-e) Failure to conduct the designated UST operator visual inspection at least once every 30 days. <br /> The following was observed on the designated operator's monthly inspection reports(December 2018-June 2019): <br /> -The"N/NA" in sections VII through XI were not fully explained on the inspection reports. <br /> -Reports were missing date, name and signature of the UST owner/operator. <br /> During the visual inspection,the designated operator shall check all required testing and maintenance for the UST <br /> system have been completed and shall check all required items on the report. Ensure that designed operators <br /> performing visual inspections at this facility are including all of the required information on the reports. <br /> This is a minor violation. <br /> Overall Inspection Comments: <br /> The monitoring system certification was conducted on 7/9/2019 and was not fully witnessed by EHD. Looked <br /> inside all sumps and UDCs. Verified sensor locations and piping communication. Verified spill bucket 5 gallon <br /> capacity. <br /> An inspection checklist was provided to the facility operator on the day of inspection. EHD has written the <br /> complete report which replaces the initial checklist. <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> FA0016523 PR0524617 SCO01 07/09/2019 <br /> EHD 23-01 Rev.09/28/2018 Page 5 of 6 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />