Laserfiche WebLink
UNDERGROUND STORAGE TANK <br /> OVERFILL PREVENTION EQUIPMENT INSPECTION REPORT FORM (Page 1 of 1 ) <br /> Type of Action ❑ Installation Inspection ❑ Repair Inspection ® 36 Month Inspection <br /> L FACILITY INFORMATION <br /> CERS ID Date of Overfill Prevention Equipment Inspection <br /> 10120456 8/15/19 <br /> Business Name (Same as Facility Name or DBA-Doing Business As) <br /> Rancho San Miguel Market <br /> Business Site Address City ZIP Code <br /> 1427 S . Airport Way Stockton 95206 <br /> Il . UNDERGROUND STORAGE TANK SERVICE TECHNICIAN INFORMATION <br /> Name of UST Service Technician Performing the Inspection (Print as shown on the ICC Certification.) Phone # <br /> Steve White (408) 971 -2445 <br /> Contractor / Tank Tester License # ICC Certification # ICC Certification Expiration Date <br /> 485184 8898679 5/10/20 <br /> Overfill Prevention Equipment Inspection Training and Certifications (List applicable certifications.) <br /> 10162437101C24135 <br /> HIS OVERFILL PREVENTION EQUIPMENT INSPECTION INFORMATION <br /> Inspection Method ® Manufacturer Guidelines (Specify) : OPW <br /> Used : <br /> ❑ Industry Code or Engineering Standard (Specify): <br /> ❑ Engineered Method (Specify): <br /> Attach the inspection procedures and all documentation required to determine the results. # of Attached Pages <br /> TANK ID : (By tank number, stored product, etc.) T2 91 <br /> What is the tank inside diameter? (Inches) 112 <br /> Is the fill piping secondarily contained? ❑ Yes ❑ No ® Yes ❑ No ❑ Yes ❑ No ❑ Yes ❑ No <br /> Is the vent piping secondarily contained? ❑ Yes ❑ No ❑ Yes ❑✓ No ❑ Yes ❑ No ❑ Yes ❑ No <br /> Overfill Prevention Equipment Manufacturer(s) OPW <br /> 61 -SO <br /> What is the overfill prevention equipment response ❑ Shuts Off Flow Shuts Off Flow ❑ Shuts Off Flow ❑ Shuts Off Flow <br /> when activated? <br /> (Check all that apply.) ❑ Restricts Flow ❑ Restricts Flow El Restricts Flow El Restricts Flow <br /> ❑ AN Alarm © AN Alarm ❑ AA/ Alarm ❑ AN Alarm <br /> Are flow restrictors installed on vent piping? <br /> El Yes ❑ No 0Yes ❑ No ❑ Yes [I No E3 Yes [] No <br /> At what level in the tank is the overfill prevention set <br /> to activate? (Inches from bottom of tank.) 98. 75 <br /> What is the percent capacity of the tank at which the <br /> overfill prevention equipment activates? 93 . 3% <br /> Is the overfill prevention in proper operating condition ❑ Yes © Yes ❑ Yes ❑ Yes <br /> to respond when the substance reaches the <br /> appropriate level? ❑ No (Specify in V.) ❑ No (Specify in V.) ❑ No (Specify in V.) ❑ No (Specify in V.) <br /> IV. SUMMARY OF INSPECTION RESULTS <br /> Overfill Prevention Inspection Results ❑ Pass ❑ Fail ® Pass ❑ Fail ❑ Pass ❑ Fail [] Pass ❑ Fail <br /> V. COMMENTS <br /> Any items marked "Fail' must be explained in this section. Any additional comments may also be provided here. <br /> Have to return to remove 87 drop tube <br /> via CERTIFICATION BY UST SERVICE TECHNICIAN CONDUCTING THIS INSPECTION <br /> I hereby certify that the overfill prevention equipmentwas inspected in accordance with California Code of Regulations , Title 23, <br /> Division 3, Chapter 16, Section 2637 . 2 and all the information contained herein is accurate. <br /> UST Service Technician Signature <br /> if the facility has more components than this form accommodates, additional copies of this page may be attached. <br /> CERS = California Environmental Reporting System, ID = Identification, UST = Underground Storage Tank, ICC = International Code Council, AN = Audible and Usual <br />