Laserfiche WebLink
LINE & LEAK DETECTOR TEST REPORT <br /> SITE : CHEVRON CORPORATE <br /> Identify Time Log of Test Procedures VOLUME REMARKS <br /> Each Line ( Military) Ambient Temperature psi READING NET <br /> Weather, Etc . BEFORE AFTER BEFORE AFTER CHANGE Conclusions , Repairs , Comments <br /> 87 900 PRE TEST 60 <br /> 915 BEGIN TEST 50 <br /> 930 50 450 . 0450 . 0450 . 0000 <br /> 945 50 50 . 0450 . 0450 . 0000 . 0000 <br /> 950 BLEED BACK 50 0 . 0450 . 0850 . 0400 <br /> 91 900 PRE TEST 60 <br /> 915 BEGIN TEST 50 <br /> 930 50 50 . 0450 . 0450 . 0000 <br /> 945 50 50 . 0450 . 0450 . 0000 . 0000 <br /> 950 BLEED BACK 50 0 . 0200 . 0610 . 0410 <br /> DIESEL 900 PRE TEST 60 <br /> 915 BEGIN TEST 50 <br /> 930 50 50 . 0450 . 0450 . 0000 <br /> 945 50 50 . 0450 . 0450 . 0000 . 0000 <br /> 951 BLEED BACK 50 0 . 0610 . 0990 . 0380 <br /> Page 2 of 2 <br />