Laserfiche WebLink
SAN" J D�l+ �� I 11411" Environmental Health Department <br /> COUNTY— <br /> Underground <br /> �l O U N T Y— <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> COSTCO WHOLESALE#658 T3250 W GRANT LINE RD TRACY September 26 2019 <br /> Single-Walled Non-Pressurized Piping <br /> 402 CCR 2643(d) Failure to conduct monitoring/maintain records for single-walled conventional suction(pre-1984) ❑V ❑R ❑COS <br /> 403 CCR 2643(d),2661(f) Failure to conduct 0.1 gph test for single-walled conventional suction systems(pre-Jan 1984) ❑V ❑R ❑COS <br /> 404 CCR 2643(e),2661(f) 0.1-gph line test for single-walled gravity piping not performed biennialy or post repair(pre-1984) ❑V ❑R ❑COS <br /> Other Violations <br /> 2010 See below Unlisted General violation ❑V ❑R ❑COS <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 109 CCR 2637(a-d), 2712 Failed to test secondary containment, or failed to maintain test records for 36 months. <br /> Secondary containment test for SR0078543 was performed on 4/11/2018 and six month testing was due by October <br /> 2018. Testing was completed on 11/15/2018, 1 month late. Secondary containment testing is required six months <br /> after installation and at least every 36 months after. Take all necessary precautions to ensure testing is performed in <br /> a timely manner. <br /> This is a Class II violation. <br /> 306 CCR 2630(d), 2641(a) Monitoring equipment is not installed or maintained to detect a leak at the earliest opportunity. <br /> The site is using flex piping. Test boots were not pulled back, but drain valves were unplugged. Hoses were observed <br /> connected to the test boot drain valves on the product pipes in the UDCs. Several of the drain valves were pointed up <br /> instead of down. Several hoses were observed with loops and upward sections. The hoses were not positioned and <br /> maintained for the sensors to detect a leak at the earliest opportunity. Monitoring equipment shall be maintained to <br /> be able to detect a leak at the earliest possible opportunity. Immediately make all necessary changes to ensure that <br /> all monitoring equipment is maintained and located to detect a leak at the earliest opportunity. <br /> This is a Class II violation. <br /> 313 HSC 25290.1,25290.2, 25291 Failure to construct, operate, and maintain primary containment as product-tight. <br /> Fuel drips were observed under dispenser 11/12. Dark staining was observed under the drips. All primary <br /> containment for the UST system must be product tight. Immediately have a properly licensed,trained, and certified <br /> contractor repair or replace the failed component(s), under permit and inspection of the EHD if necessary. <br /> This is a minor violation. <br /> 319 CCR 2635, 2637.1,2665, 2712 No spill bucket,failed to contain 5 gallons, no means to keep it empty, or failed to be <br /> tested. <br /> The additive and 87B spill containers failed when tested. Noticeable drips were observed from both containers during <br /> testing. All spill containers shall have a minimum capacity of five gallons and be capable of containing a spill or overfill <br /> until it is detected or cleaned up. Immediately contact a properly licensed,trained, and certified contractor to repair or <br /> replace the spill containers under permit and inspection of the EHD. <br /> This is a minor violation. <br /> Overall Inspection Comments: <br /> FA0013810 PR0518288 SCO01 09/26/2019 <br /> EHD 23-01 Rev.08/27/2019 Page 4 of 5 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />