Laserfiche WebLink
SANJ OA U I Environmental Health Department <br /> COUNTY <br /> — <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> 76 EXPRESS TIGER NO 1 5777 S FRENCH CAMP RD STOCKTON January 15 2019 <br /> Single-Walled Non-Pressurized Piping <br /> 404 CCR 2643(e),2661(f) Biennial 0.1 gph line integrity test for single-walled gravity piping not performed(pre-Jan 1984) ❑V ❑R ❑COS <br /> Other Violations <br /> 2010 See below Unlisted General violation ❑V ❑R COS <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 103 HSC 25292.2, 25299.30 Failure to submit and maintain complete and current financial responsibility documents. <br /> Financial responsibility documents have not been submitted to the EHD. The most recent financial responsibility <br /> documents are dated 11/29/17. Current financial responsibility documents are required to be submitted annually. <br /> Immediately log into the California Environmental Reporting System (CERS) at http://cers.calepa.ca.gov/, and upload <br /> the required documents. <br /> This is a minor violation. <br /> 104 CCR 2711 UST operating permit application for facility and tank information not submitted or current. <br /> UST Tank Information forms are not current in CERS. <br /> -The UDC primary material is incorrectly listed as fiberglass. The facility is using steel Bravo boxes. <br /> Any change of information must be updated in CERS within 30 days of the changes. Immediately log into CERS, <br /> update the required information, and submit for review by the EHD. <br /> This is a repeat violation, Class II. <br /> 105 CCR 2632(d)(1), 2634(d) Failed to have an approved UST monitoring plan. <br /> The monitoring plan is not current and/or not approved by the EHD. <br /> -All three monitoring plans incorrectly list the leak detectors as VMI LD 2000. The 87 and 91 tanks are using VMI 99 <br /> LD-2000 leak detectors. The diesel tank is using VMI LD 3000 and FE Petro STP-MLD leak detectors. <br /> The monitoring plan must be uploaded to the California Environmental Reporting System (CERS). Immediately log <br /> into CERS, make the necessary changes, and submit for review by the EHD. <br /> This is a minor violation. <br /> 106 CCR 2632(d)(2), 2634(e) Failed to have an approved UST response plan. <br /> The response plan is not current and/or not approved by the EHD. The response plan submitted includes outdated <br /> manager information. The response plan must be uploaded to the California Environmental Reporting System (CERS). <br /> Immediately log into CERS, upload the completed form, and submit for review by the EHD. Ensure a copy is available <br /> for inspection at any time. <br /> This is a minor violation. <br /> FA0006977 PR0505746 SCO01 01/15/2019 <br /> EHD 23-01 Rev.09/28/2018 Page 4 Of 9 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />