LDT 5000 Field Test Apparatus Page 1 of 1 <br /> 40W Tanknology Line Leak Detector Test <br /> Work Order: 2339855 Date : 4 /30/2019 <br /> Site Name / ID : 7 - ELEVEN #32190 , MKT 2368 / 32190 <br /> Address : 4943 S . KINGSLEY ( FRONTAGE RD) HWY 99 @ ARCH AIRPORT RD <br /> City : STOCKTON State : CA Zip : 95206 <br /> Tank ID T4 T5 T6 <br /> Product RUL MUL PUL <br /> Product Line 1 1 1 <br /> Tested From 2 2 2 <br /> Existing/New Existing Existing Existing <br /> Mechanical / Electronic Electronic Electronic Electronic <br /> Manufacturer/Model Veeder Root PLLD Veeder Root PLLD Veeder Root PLLD <br /> Serial No . 285067 233415 870131 <br /> Pump Operating Pressure ( psi ) 30 . 00 29 . 00 32 . 00 <br /> Calibrated Leak (ml /min ) 189 . 0 189 . 0 189 . 0 <br /> Calibrated Leak (gph ) 3 . 00 3 . 00 3 . 00 <br /> Holding PSI <br /> ' NIA for Electronic LD' s <br /> Resiliency (ml) <br /> ` NIA for Electronic LD' s <br /> Metering PSI <br /> ` NIA for Electronic Lo 's <br /> Opening Time (sec) <br /> N/A for Electronic LD' s <br /> est Results Pass Pass Pass <br /> Technician Comments : <br /> Technician Name : Jesus Saldivar Certification #: 115237 <br /> Technician Signature : �� 6 ��� Expire Date : 1 /27/2022 <br /> Environmental Compliance for Petroleum Systems <br /> © 2019 Tankndogy Inc., Austin, Tx. All rights reserved. tanknology.com <br />