Laserfiche WebLink
Al <br /> n � H H AL1. 1HG1 701 N , Parkcenter Drive, Santa Ana , to 92705 <br /> p , 714/560/8222 www.taitcorn <br /> Identification of Test Procedures for Secondary Containment Testing <br /> To Whom It May Concern : <br /> Tait Environmental Services, Inc . , utilizes the following procedures when conducting Secondary <br /> Containment Testing : <br /> 1 ) Containment Sumps, Transition Sumps, UDCs — Tait follows PEI - RP1200- 17 Section 6 . 6 for the <br /> accelerated test method . Tait uses the Incon TS- 1000 hydrostatic test equipment following the <br /> attached procedures . <br /> 2 ) Spill Buckets, Direct Bury & Contained in Sumps — Spill buckets contained in sumps are tested <br /> per PEI - 120047, Section 6 . 2, however Tait Pass/ Fail threshold is 0" drop in one hour. Direct Bury <br /> Spill Buckets are test the same as containment sumps per PEI - 1200- 17 , Section 6 . 6 . <br /> 3 ) Tank Annular Space — testing is conducted per PEI4200- 17, Section 4 . 2 <br /> 4) Piping Secondary Containment — Testing is conducted per PEI - RP1200- 17, Section 5 . 3 <br /> Please consider this letter as our Test Procedure utilized when conducting Secondary Containment <br /> Testing in lieu of either parts or the whole RP1200 document due to copyright infringement . <br />