Laserfiche WebLink
A J OA U I Environmental Health Department <br /> COUNTY <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> MARCH AND BIANCHI INC 1 1916 E MARCH LN, STOCKTON November 19, 2020 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 110 CCR 2715(a)(1)(A), 2715(a)(2) Failure to submit the "Underground Storage Tank Statement of Understanding and <br /> Compliance Form". <br /> OBSERVATION: The Underground Storage Tank Statement of Understanding and Compliance Form was not found <br /> in CERS. <br /> REGULATION GUIDANCE: This form must be uploaded to the California Environmental Reporting System (CERS). <br /> CORRECTIVE ACTION: Immediately log into the California Environmental Reporting System (CERS) at <br /> http://cers.calepa.ca.gov and upload the Underground Storage Tank Statement of Understanding and Compliance <br /> Form for this facility. <br /> This is a repeat violation, Class II. <br /> 203 CCR 2712(b)(1-2) Failure to maintain monitoring records for 36 months and maintenance records for 60 months. <br /> OBSERVATION: Maintenance and monitoring records for the last three years were not found on site. <br /> -The 11/21/2018 Overfill prevention test results were not found on site during inspection <br /> -The 2017 Monitoring system certification test result were not found on site during inspection <br /> -Test results for repairs L18 of the 87 fill sump , diesel fill sump and UDC's 11/12, 9/10 sensors(12/18/2019)were <br /> not found on site during the inspecton. <br /> REGULATION GUIDANCE: These records shall be maintained on site for at least three years. Monitoring records <br /> include: (1) date and time of all monitoring or sampling; (2) monitoring equipment calibration and maintenance <br /> records; (3) results of any visual observations; (4) results of sample analysis performed a lab or in the field; (5) logs <br /> of all readings of gauges or other monitoring equipment, ground water elevations, or other test results; (6) results of <br /> inventory readings and reconciliations. <br /> CORRECTIVE ACTION: Immediately locate and maintain all missing maintenance and monitoring records for the <br /> last three years on site and submit copies to the EHD. <br /> This is a minor violation. <br /> 205 CCR 2712(1) Failure to have current UST Monitoring Plan readily accessible at the facility. <br /> OBSERVATION: An approved copy of the monitoring plans were not available for inspection. <br /> REGULATION GUIDANCE: A copy of these plans shall be accessible on site at all times. <br /> CORRECTIVE ACTION: Immediately locate and retain a copy on site. <br /> This is a repeat violation, Class II. <br /> FA0018792 PR0527728 SCO01 11/19/2020 <br /> EHD 23-01 Rev.9/16/2020 Page 6 of 9 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />