Laserfiche WebLink
TABLE#2 RECOMMENDED MINIMUM VERIFICATION ANALYSES <br /> FOR UNDERGROUND STORAGE TANK INVESTIGATIONS <br /> TANK TANK TPH-G TPH-D BTX&E CL HC TOTAL <br /> # CONTENTS MTBE OXYGENATES METALS PCB <br /> 8015 8015 8020 8010 LEAD CAP/AES <br /> (MTBE,TBA,DIPE, 827 <br /> 8020 0 <br /> 8260 8260 8260 8240 7420 ETBE,TAME) Or 8080 <br /> 8260 7421 82601,2 DCA&EDB AA <br /> 8260 <br /> LEADED GAS X X X X <br /> UNL GAS X X <br /> X <br /> DIESEL X X <br /> KEROSENE X X X <br /> LINK FUEL X X X X X <br /> PROD.OIL X X X <br /> CHLOR. <br /> SOLVENTS X X X <br /> NONCHLOR <br /> SOLVENTS X X X <br /> WASTE\USED OIL <br /> OR <br /> UNKNOWN X X X X X X X <br /> CONTENTS <br /> Notes: <br /> 1. EPA Method 82606 analyses must include all analytes listed in the method plus fuel oxygenates methyl- <br /> tertiary-butyl ether(MTBE),diisopropyl ether(DIPE),ethyl-tertiary-butyl ether(EtBE), tertiary-amyl-methyl <br /> ether(TAME),tertiary-butanol(TBA), methanol and ethanol and fuel additives 1,2-dichlorcethene(1,2-DCA) <br /> and ethylene dibromide(EDB or 1,2-dibronwethane). <br /> 2. If pentachlorophenol (PCP)is identified, analyze the soil and/or water sample for dioxins and furans by EPA <br /> Method 8290 and pesticides by EPA Method 8081A. <br /> 3. METALS ICAP or AA Inductively Coupled Plasma Atomic Emission Spectrometry 6010 or Atomic <br /> Absorption Spectrometry 7000. Metals:Cadmium,Chromium III and VI, Lead,Zinc and Nickel. <br /> 4. Non-proprietary, performance based analytical methods may be used with approval of Regional Board staff. <br /> EH23046 (Reviscd8/I/II) 7 <br />