Laserfiche WebLink
A J OA U I Environmental Health Department <br /> COUNTY <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: I Date: <br /> SHERIFFS OPERATIONS CTR#1 7000 N MICHAEL CANLIS RD, FRENCH CAMP January 22, 2021 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 203 CCR 2712(b)(1-2) Failure to maintain monitoring records for 36 months and maintenance records for 60 months. <br /> OBSERVATION: Maintenance and monitoring records for the last three years were not found on site. <br /> -The 10/11/2018 Overfill prevention test results were not on site during the inspection <br /> -The 08/29/2018 Secondary containment test results were not on site during the inspection. <br /> -During the 2020 inspection liquid was observed under the diesel dispenser 3/4 indicating a leak in the primary <br /> containment. Provide justification for the repairs or replacement of this component. <br /> REGULATION GUIDANCE: These records shall be maintained on site for at least three years. Monitoring records <br /> include: (1)date and time of all monitoring or sampling; (2) monitoring equipment calibration and maintenance <br /> records; (3) results of any visual observations; (4) results of sample analysis performed a lab or in the field; (5) logs <br /> of all readings of gauges or other monitoring equipment, ground water elevations, or other test results; (6) results of <br /> inventory readings and reconciliations. <br /> CORRECTIVE ACTION: Immediately locate and maintain all missing maintenance and monitoring records for the <br /> last three years on site and submit copies to the EHD. <br /> This is a repeat violation, Class II. <br /> 205 CCR 2712(1) Failure to have current UST Monitoring Plan readily accessible at the facility. <br /> OBSERVATION: An approved copy of the monitoring plans were not available for inspection. <br /> REGULATION GUIDANCE: A copy of these plans shall be accessible on site at all times. <br /> CORRECTIVE ACTION: Immediately locate and retain a copy on site. <br /> This is a minor violation. <br /> Overall Inspection Comments: <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, by 02/21/2021 . <br /> To minimize person to person contact EHD is choosing to write the name of person receiving the report instead <br /> of having them sign. Starting September 1, 2018, all in-office CERS help will be provided at EHD hourly rate <br /> ($152). To schedule an appointment, please call (209) 468-3420. <br /> Documents provided during inspection: Return to compliance certifiation form, corrective action statement form <br /> and a list of approve CUPA schedule free classes. <br /> FA0003787 PR0232437 SCO01 01/22/2021 <br /> EHD 23-01 Rev.9/16/2020 Page 5 of 6 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />