Laserfiche WebLink
Underground Storage Tank <br /> Overfill Prevention Equipment Inspection Report <br /> 6. OVERFILL PREVENTION EQUIPMENT DETAILS <br /> Tank ID (one OPE per column) T-1 87 T-2 DFR <br /> Are both vent and tank riser ❑ Yes ❑ Yes ❑ Yes ❑ Yes <br /> piping secondarily contained? ® No ® No ❑ No ❑ No <br /> OPE Model OPW OPW <br /> What is the OPE response when ® Shut off ® Shut off ❑ Shut off ❑ Shut off <br /> activated? Flow Flow Flow Flow <br /> (Check all that apply.) ®Restricts ®Restricts ❑Restricts ❑Restricts <br /> Flow Flow Flow Flow <br /> ❑ Audible ❑ Audible ❑ Audible ❑ Audible <br /> Alarm Alarm Alarm Alarm <br /> ❑ Visual ❑ Visual ❑ Visual ❑ Visual <br /> Alarm Alarm Alarm Alarm <br /> Are flow restrictors installed on ❑ Yes*® No ❑ Yes*® No ❑ Yes*❑ No ❑ Yes*❑ No <br /> vent piping that may interfere <br /> with the OPE operation? <br /> At what level in the tank is the 86" 85.625" <br /> OPE set to activate? Inches <br /> What is the percent capacity of 95% 94.5% <br /> the tank at which the OPE <br /> Is the OPE in proper operating ® Yes❑ No ® Yes❑ No ❑ Yes❑ No ® Yes❑ No <br /> condition to respond when the <br /> stored substance reaches the <br /> designated regulatory level? <br /> 7. SUMMARY OF TESTING RESULTS <br /> OPE Inspection Results ® Pass❑ Fail ® Pass❑ Fail I ❑ Pass❑ Fail--E] Pass❑ Fail <br /> 8. COMMENTS <br /> Describe all results marked "Fail'and each proposed remedy. <br /> * Mark here if: <br /> ❑ Flow restrictors interfere with overfill prevention and equipment repairs required. <br /> Additional copies of this page may be attached. <br /> Attach tank chart(s), measurements, calculations, and In-Tank Setup report(s) <br /> Page 2 of 2 <br />