Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by ® Manufacturer © Industry Standard ❑ Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum ® Hydrostatic <br /> Test Equipment Used: F.F.S. Incon TS-STS Sump Tester w/ + or — 0.002" graduations <br /> Sump/UDC ID Disp 1/2 87 STP DFR STP <br /> Sump Manufacturer Bravo Western Western <br /> Fiberglass Fiberglass <br /> Sump Depth (inches) 8" 65" 65" <br /> Sump Bottom to Top of 2" 16" 16" <br /> Highest Pipe <br /> Penetration (inches) <br /> Test Start Time NA 10:11am 11:07am <br /> Initial Reading NA 3.4524" 2.2859" <br /> Test End Time NA 10:26am 11:22am <br /> Final Reading NA 3.4522" 2.2827" <br /> Change in Reading Visual Failure -0.0002" -0.0032" <br /> Pass/Fail Criteria +/- 0.002 +/- 0.002 +/- 0.002 <br /> Tightness Test Results ❑ Pass © Fail ® Pass ❑ Fail ❑ Pass ® Fail ❑ Pass ❑ Fail <br /> Sump/UDC ID <br /> Sump Manufacturer <br /> Sump Depth (inches) <br /> Sump Bottom to Top of <br /> Highest Pipe <br /> Penetration (inches) <br /> Test Start Time <br /> Initial Reading <br /> Test End Time <br /> Final Reading <br /> Change in Reading <br /> Pass/Fail Criteria <br /> Tightness Test Results ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail'and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />