Laserfiche WebLink
Underground Storage Tank <br /> Overfill Prevention Equipment Ins ection Report Form <br /> 6. OVERFILL PREVENTION EQUIPMENT DETAILS <br /> Ta n k I D (One OPE per column) 87 91 DSL E 85 <br /> Are both vent and tank riser piping ❑ Yes ❑ Yes ❑ Yes ❑ Yes <br /> secondarily contained? No ® No 50 No ❑ No <br /> OPE Model OPW OPW OPW OPW <br /> Tank Manufacturer Cont Sol Cont Sol Cont Sol Cont Sol <br /> ® Shuts off ® Shuts off ® Shuts off ® Shuts off <br /> Flow Flow Flow Flow <br /> What is the OPE response when ❑ Restricts ❑ Restricts ❑ Restricts ❑ Restricts <br /> activated? Flow Flow Flow Flow <br /> (Check a#that apply.) ❑ Audible ❑ Audible ❑ Audible ❑ Audible <br /> Alarm Alarm Alarm Alarm <br /> ❑Visual ❑Visual ❑Visual []Visual <br /> Alarm Alarm Alarm Alarm <br /> Are flow restrictors installed on vent ❑ Yes ❑ Yes ❑ Yes ❑ Yes <br /> piping that may interfere with the OPE ® No ® No ® No ® No <br /> operation? <br /> At what level in the tank is the OPE set to 109 108 108 108 <br /> activate? (Inches from bottom of tank) <br /> What is the percent capacity of the tank in 96% 98% 96% 98% <br /> which the OPE activates? <br /> Is the OPE in proper operating condition ® Yes ® Yes ® Yes ® Yes <br /> to respond when the stored substance ❑ No ❑ No ❑ No ❑ No <br /> reaches the designated regulatory level? <br /> 7. SUMMARY OF TESTING RESULTS <br /> OPE Inspection Results ❑ Pass ❑ Pass ❑ Pass ❑ Pass <br /> ® Fail ® Fail ® Fail ® Fail <br /> 8. COMMENTS <br /> All drop tubes failed as they are over 95% per regulation. Need to return to replace the drop tubes <br /> and retest. <br /> Page 2 of 2 <br />