Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 6. TANK SECONDARY CONTAINMENT TEST (ANNULAR) <br /> Test Method Developed by ❑ Manufacturer ® Industry Standard ❑ Professional Engineer <br /> Test Type — El Pressure ® Vacuum ❑ Hydrostatic <br /> Test Equipment Used: PEI/ RP1200/ 10Hg for 1 hr <br /> Tank ID 87/91 DSUE85 <br /> Tank Manufacturer Unknown Unknown <br /> Tank Capacity N/A N/A <br /> Test Start Time 9:45 11:35 <br /> Initial Reading -10 -10 <br /> Test End Time 10:45 12:35 <br /> Final Reading -10 -10 <br /> Change in Reading 0 0 <br /> Pass/Fail Criteria 0 0 0 0 <br /> Tightness Test Results ® Pass ❑ Fail I ® Pass ❑ Fail I ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> 7. PIPE SECONDARY CONTAINMENT TEST (SEC LINE) <br /> Test Method Developed by ❑ Manufacturer ® Industry Standard ❑ Professional Engineer <br /> Test Type ® Pressure ❑ Vacuum ❑ Hydrostatic <br /> Test Equipment Used: PEI/ RP1200/5 psi for 1 HR <br /> Pipe Run ID 87 91 <br /> Pipe Manufacturer Unknown Unknown <br /> Test Start Time 11:10 9:45 <br /> Initial Reading 5 5 <br /> Test End Time 12:10 10:45 <br /> Final Reading 5 5 <br /> Change in Reading 0 0 <br /> Pass/Fail Criteria 0 0 0 0 <br /> Tightness Test Results ® Pass ❑ Fail ® Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Pipe Run ID <br /> Pipe Manufacturer <br /> Test Start Time <br /> Initial Reading <br /> Test End Time <br /> Final Reading <br /> Change in Reading <br /> Pass/Fail Criteria 0 0 0 0 <br /> Tightness Test Results ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Page 2 of 6 <br />