My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
COMPLIANCE INFO_2021
Environmental Health - Public
>
EHD Program Facility Records by Street Name
>
Y
>
YOSEMITE
>
1001
>
2300 - Underground Storage Tank Program
>
PR0231876
>
COMPLIANCE INFO_2021
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
12/20/2021 5:00:25 PM
Creation date
1/14/2021 7:56:51 AM
Metadata
Fields
Template:
EHD - Public
ProgramCode
2300 - Underground Storage Tank Program
File Section
COMPLIANCE INFO
FileName_PostFix
2021
RECORD_ID
PR0231876
PE
2361
FACILITY_ID
FA0000421
FACILITY_NAME
DINO MART
STREET_NUMBER
1001
Direction
E
STREET_NAME
YOSEMITE
STREET_TYPE
AVE
City
MANTECA
Zip
95336
CURRENT_STATUS
01
SITE_LOCATION
1001 E YOSEMITE AVE
P_LOCATION
04
P_DISTRICT
003
QC Status
Approved
Scanner
SJGOV\gmartinez
Tags
EHD - Public
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
121
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
SANJOAQUIN <br />COUNTY— <br />Environmental Health Department <br />Underground Storage Tank Program Inspection Report <br />Facility Name: <br />Facility Address: <br />1 <br />Date: <br />DINO MART <br />1001 E YOSEMITE AVE, MANTECA <br />April 26, 2021 <br />SUMMARY OF VIOLATIONS <br />(CLASS I, CLASS II, or MINOR - Notice to Comply) <br />Item # <br />Remarks <br />319 <br />CCR 2635, 2637.2, 2665, 2712 Failure to comply with overfill prevention equipment requirements. <br />OBSERVATION: The MECHANICAL FLAPPER, used as the overfill prevention system is not currently functional <br />on the diesel UST. <br />REGULATION GUIDANCE: All UST systems must be equipped with an approved, functional overfill prevention <br />device at all times during delivery operations. <br />CORRECTIVE ACTION: Immediately discontinue deposition of petroleum into this tank until the component is <br />repaired or replaced by a properly licensed, trained, and certified contractor under permit and inspection of the EHD. <br />If the failed component can't be replaced immediately, there is a possibility that the [GRADE] UST system may be <br />red tagged to prevent fuel inputs. <br />This is a repeat violation, Class II. <br />Overall Inspection Comments: <br />Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br />documenting the corrective actions that have been or will be taken for each violation, and any supporting <br />paperwork, by 05/26/2021 . <br />To minimize person to person contact EHD is choosing to write the name of person receiving the report instead <br />of having them sign. Starting September 1, 2018, all in -office CERS help will be provided at EHD hourly rate <br />($152). To schedule an appointment, please call (209) 468-3420. <br />Documents provided during inspection: Return to compliance certification form, corrective action statement form <br />and a list of approve CUPA free training classes. <br />AFTER THE COMPLIANCE DATE, EHD WILL BILL FOR ALL TIME AND ACTIVITIES ASSOCIATED WITH BRINGING <br />THIS FACILITY BACK INTO COMPLIANCE. <br />THIS FACILITY IS SUBJECT TO REINSPECTION AT ANY TIME AT EHD'S CURRENT HOURLY RATE. <br />Received by: Date: April 26, 2021 <br />Inspector: <br />Inspector Phone: <br />Printed Name and Title: <br />PAUL NSO, EH Specialist <br />(209) 616-3049 <br />Avinash Singh, Owner <br />FA0000421 PR0231876 SC333 04/26/2021 <br />EHD 23-01 Rev. 9/16/2020 Page 7 of 7 Underground Storage Tank Program OIR <br />1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />
The URL can be used to link to this page
Your browser does not support the video tag.