Laserfiche WebLink
/y` 7 io1 <br /> I <br /> Appendix B 6141 z.I <br /> S 1 7150 Overfill Valve in Tank Shut off Level Worksheet <br /> Important: This is meant to be supplemental worksheet and not a substitute to following the installation <br /> manual instructions, All length measurements are in inches. Please contact the Authority Having Jurisdic- <br /> tion (AHJ)and review local,state,and national codes to determine the regulatory requirements governing <br /> shut-off capacity in your region,as well as-take into account other considerations such as extreme tank tilt. <br /> Take the following measurements with tie valve in i <br /> stalled in the tank. - �- <br /> Distance from the 71 SO inlet tube flange to the cast <br /> lug in the 71 SO body(see figures),upper tube length. <br /> Note: the Upper Tube Length must be at least 16"to in- <br /> elude the protective bend in the tube. ,r <br /> (D)_ 41- _ If 3 E Vii_ <br /> Distance from the 71 SO inlet tube flange to the top and �`� <br /> bottom of lower tube,valve length. <br /> I <br /> (W)_ I IS (D) <br /> Upper <br /> (U)= I Z�' L+'�' Tube <br /> Distance from the 71 SO inlet tube flange to the bottom <br /> of the tank. Note:If a tank bottom protector is present it <br /> may be necessary to add this thickness to dimension I <br /> (OPW 6111 &61 TP models add 0.6") (W)Valve <br /> (B)= 137- -..- Length, 1 <br /> bottom of <br /> From the tank calibration chart provided by tank manu� ! y cut <br /> facturer find the dipstick number(Y)which corresponds = <br /> to the 100%volume. ! (8) <br /> (Y)=- st-__ r'-` To Tank 4 <br /> (Y) <br /> 1. To determine shut-off percentage: Tank <br /> Subtract upper tube length (D)frorn distance to tank (U)Valvet <br /> Chart <br /> bottom (B) r� Length, 100% ` <br /> (X)=(B)-(D)-2"= l l_ a -_--------- top of cut 3 Volume <br /> ---- -._ -- Dipstick <br /> Using the tank calibration chart provided by the tank d "� <br /> manufacturer determine the tank capacity at the 00/ volume O tank cal- <br /> culated Y i <br /> culated(X)dimension and the 1 <br /> capacity. <br /> -I <br /> (X)tank capacity in gallons= ��5�> 7' <br /> (Y)tank capacity in gallon;:- q06;' 30 L k <br /> 50%_(X)capacity t(Y)capacity x1 a ��'� ��'� `-- <br /> Note: The overfill valve must be installed per AM require- <br /> ments and ail applicable local,state,and national codes. If <br /> the overfill valve is set above the allowable shut-off percent- <br /> age_the;overfill valve must be removed and replaced. t or <br /> reference 40 CFR part 280 Subpart B Section 280.20 overfill <br /> valves should be set to a maximum of 95%. <br /> 1? <br />