Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8 . SUMP/UDC TES's <br /> Test Method Developed by ❑ Manufacturer ❑ Industry Standard ® Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum ® Hydrostatic <br /> Test Equipment Used : Caldwell Level Change Indicator <br /> PSump <br /> /UDC ID UDC 13 & 14A UDC 14 & 15A UDC 15 & 16 UDC 17 & 18 <br /> Manufacturer Bravo Syscsc Bravo Syscsc Bravo Syscsc Bravo Syscsc <br /> Depth ( inches ) 10 " 10 " 10 " 10 " <br /> Sump Bottom to Top of BP gp gp BP <br /> Highest Pipe Penetration <br /> ( inches ) <br /> Test Start Time 11 : 47 11 : 52 11 : 57 12 : 02 <br /> Initial Reading . 001 . 001 2001 . 001 <br /> Test End Time 12 : 17 12 : 22 12 : 27 12 : 32 <br /> Final Reading . 001 . 001 . 001 . 001 <br /> Change in Reading 0 0 0 0 <br /> j Pass/Fail Criteria > m002 > . 002 > . 002 > v002 <br /> no Tightness Test Results ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail <br /> Sump/UDC ID <br /> Sump Manufacturer <br /> Sump Depth ( inches ) <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration <br /> ( inches ) <br /> Test Start Time <br /> Initial Reading <br /> Test End Time <br /> Final Reading <br /> Change in Reading <br /> Pass/Fail Criteria <br /> Tightness Test Results ❑ :Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail" and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section . <br />