Spill Prevention, Control and Countermeasure Plan <br /> For Northern California Youth Correctional Center <br /> Table C-1. Oil Storage Tanks Continue <br /> Capacity <br /> Tank Location and Purpose (gallons) Contents Tank Type Comment' <br /> Central Kitchen 100 Diesel AST—Steel tank 1. Direct visual volume gauge. <br /> (Emergency Generator Belly integrated with 2. No automatic interstitial space monitoring provided. <br /> Tank) generator 3. Normal and emergency vents provided. <br /> Delta Room 100 Diesel AST—Steel tank 4. Tank properly grounded. <br /> (Emergency Generator Belly integrated with 5. Tank bolted to concrete pad for earthquake restraint. <br /> Tank) generator 6. Rubber Berm installed on concrete pad for secondary <br /> O.H. Close Education 100 Diesel AST—Steel tank containment. <br /> (Emergency Generator Belly integrated with 7. Vehicle protection provided by generator package and fence. <br /> Tank) generator 8. Spill kit present at the Auto Shop and Plant Operations <br /> O.H. Unit 1 100 Diesel AST—Double-wall steel 1. Direct visual volume gauge. <br /> (Emergency Generator) tank integrated with 2. Normal and emergency vents provided. <br /> generator 2. Tank properly grounded. <br /> O.H. Unit 4 100 Diesel AST—Double-wall steel 3. Tank bolted to concrete pad for earthquake restraint. <br /> (Emergency Generator) tank integrated with 4. Vehicle protection provided by generator package and fence. <br /> generator 6. Spill kit present at the Auto Shop and Plant Operations <br /> a Comments associated with multiple tanks at one location are provided in same row. <br /> AST—aboveground storage tank <br /> C-2 <br />