J.M. Equipment Co.Inc.,Facility(11754), Used Oil Tank, 22§CCR 66265.192&STI-SP0011 November 2019 <br /> 4.0 Inspection <br /> 4.1 Results: <br /> 4.1.1 Foundation: <br /> The Used Oil tank is currently sitting on the concrete floor. The tank is not currently <br /> secured to the foundation by any mechanical means. <br /> 4.1.2 Containment: <br /> The Used Oil Tank is a double-walled protected aboveground tank with secondary <br /> containment capable of containing 100% of the contents and is intrinsically designed to <br /> prevent exposure to precipitation. The interstice was found to be dry during the <br /> inspection. <br /> 4.1.3 Shell: <br /> The shell is constructed of carbon steel of unknown specification. It is a horizontal <br /> cylindrical design consisting of two (2) lap-welded courses. The shell exterior was <br /> visually inspected and appears in satisfactory condition. The coating was inspected for <br /> disbonding, adhesion, deterioration, and discoloration(See Section 4.1.6). A visual <br /> inspection was conducted over the exterior shell including the shell external welds. No <br /> discrepancies were noted on the welds. The minimum design thickness requirements per <br /> UL-142 for the tank is 0.093". The UT inspection of the tank revealed no indications that <br /> the wall thickness dropped below the minimum requirements. Thickness measurements <br /> are listed in the engineering data in Appendix B. <br /> 4.1.4 Heads <br /> A visual inspection was conducted over the heads including the head-to-shell weld. No <br /> discrepancies were noted on the welds. The coating was inspected for disbonding, <br /> adhesion, deterioration, and discoloration(See Section 4.1.6). <br /> 4.1. Appurtenances: <br /> Inspected and evaluated each tank nozzle in accordance with STI SP-001. Evaluated all <br /> nozzles and reinforcement plates for leaks and corrosion. Normal venting is being <br /> provided to the tank. The primary and secondary tank are equipped with a Clay& Bailey <br /> emergency vent. Every aboveground storage tank shall have emergency relief <br /> venting...that will relieve excessive internal pressure caused by an exposure to fire <br /> (NFPA 30 22.7.1.1). The tank has a Kruger Sentry Gauge installed for the purpose of <br /> measuring the liquid level. A fast response system for determining the liquid level of <br /> each bulk storage container such as digital computers, telepulse, or direct vision gauges. <br /> If you use this alternative, a person must be present to monitor gauges and the overall <br /> filling of bulk storage containers. (40 CFR § 112.8 (c)(8)(iv)). The Used Oil tank also has <br /> an Morrison Bros overfill prevention valve installed. <br /> 4.1.6 Painting/Insulation: <br /> No coating issues were noted during the inspection. <br /> 5 <br />