Laserfiche WebLink
Underground Storage Tank <br />Secondary Containment Testing Report Form SR0082635 <br />9. COMMENTS <br />1 Hour Pressure on 87 Secondary <br />Put test boot on Secondary. Pressurized Secondary to 5 PSI. <br />Tested for 1 hour- Test Passed. <br />Remove boot after testing. <br />SB989 - Hydrostatic <br />Filled UDC with water above highest penetration. <br />Test for 1 hour- Hydrostatic Test. <br />Test Passed. <br />All tests marked "Fail' and any repairs made before or during the tightness test must be described in <br />the COMMENTS section. <br />Page 5 of 5 <br />