Elite IV Contractors <br /> Date: 8/17/2021 <br /> Inspection Request 2nd Inspection <br /> SRoo83263 (Amended) <br /> Country Mart Gas &Food <br /> 34243 S Chrisman Road Tracy, CA 95304 <br /> Date: 8/20 /2021 Friday @ 10 AM <br /> Scope of work: Replace portion of diesel product piping between dispensers 13 &14. <br /> Inspections: (2 of 3 Inspections) 2nd Inspection <br /> A) Secondary piping soap test: One hour pressure test per manufacturer's <br /> guidelines. If there are no manufacturer's guidelines, test shall be performed <br /> using an applicable method specified in an industry code or engineering <br /> standard. <br /> B) Verification of secondary piping slope at 1/8 inch per foot or greater,to a <br /> containment sump with an audible/visual alarm. <br /> C) Verification of all pipe setbacks, crossovers, and burial depth according to the <br /> Manufacturer's installation instructions and verification of appropriate piping <br /> backfill. <br /> D) 24-hour hydrostatic test on UDC sumps. <br /> Thank you, <br /> Deborah Jones <br /> Elite IV Contractors <br /> di sp atch a eliteiv.co m <br /> (209) 461-6337 <br /> Phone:(209)461-6337 Fax:(209)461-6342 2535 Wigwam Dr.Stockton,CA 95205 <br /> Email:dispatch@eliteiv.com <br />