Laserfiche WebLink
Elite IV Contractors <br /> Date: 8/30/2021 <br /> Inspection Request <br /> SRoo83263 (Amended)2 <br /> Country Mart Gas&Food <br /> 34243 S Chrisman Road Tracy, CA 95304 <br /> Date: 9/01/2021 Wednesday @ 10 AM <br /> Scope of work: Replace portion of diesel product piping between dispensers 13 & 14. <br /> Inspections: <br /> 3rd Inspection <br /> A) Sensor functionality: Functionality of the monitoring system must be verified to <br /> endure that monitoring has been restored to meet the requirements of Title 23 <br /> California Code of Regulations and the Health&Safety Code. <br /> B) Verification of the dispenser footprints contained by the under-dispenser <br /> containment sumps. Any potential leaks from piping and fuel filters must drain <br /> Directly into UDC's. <br /> Secondary containment testing for the diesel piping and four(4)newly installed UDC's is <br /> required six months after installation. Provide 48 hours notification to the EHD when <br /> this test is scheduled. <br /> (Carol Presto did say to do the Secondary testing with 3rd Inspection) <br /> 4th Inspection <br /> C) Since concrete will be broken near the Diesel tank, a secondary containment test <br /> must be performed on the Diesel tank once concrete is poured in accordance with <br /> the manufacturer's guidelines. <br /> We will schedule 6 months from now the Secondary testing again. <br /> Thank you, <br /> Deborah Jones <br /> Elite IV Contractors <br /> No <br /> Phone:(209)461-6337 Fax:(209)46i-6342 2535 Wigwam Dr.Stockton,CA 95205 <br /> Email:dispatch@eliteiv.com <br />