DATA SHEET 01 ANSUL
<br /> R-102 Restaurant
<br /> Fire Suppression
<br /> Systems
<br /> Features
<br /> ■ Low pH Agent
<br /> ■ Proven Design
<br /> ■ Reliable Gas Cartridge Operation �=
<br /> ■ Aesthetically Appealing
<br /> ■ UL Listed —Meets Requirements of UL 300
<br /> ■ ULC Listed—Meets Requirements of ULC/ORD-C1254.6
<br /> ■ CE Marked 004212
<br /> Application
<br /> The ANSULa R-102 Restaurant Fire Suppression System is an
<br /> automatic,pre-engineered,fire suppression system designed The system is capable of automatic detection and actuation
<br /> to protect areas associated with ventilating equipment includ- as well as remote manual actuation.Additional equipment is
<br /> ing hoods,ducts, plenums,and filters.The system also protects
<br /> auxiliary grease extraction equipment and cooking equipment available for building fire alarm panel connections,electrical
<br /> shutdown and
<br /> such as fryers;griddles and range tops;upright, natural charcoal, interface,and mechanical or electrical gas line
<br /> or chain-type broilers;electric, lava rock, mesquite,or gas-radiant shut-off applications.
<br /> char-broilers;and woks. The detection portion of the fire suppression system allows for
<br /> The system is ideally suitable for use in restaurants,hospitals, automatic detection by means of specific temperature-rated alloy
<br /> nursing homes,hotels,schools,airports,and other similar facilities. type fusible links,which separate when the temperature exceeds
<br /> the rating of the link,allowing the regulated release to actuate.
<br /> Use of the R-102 system is limited to indoor applications or loca-
<br /> tions that provide weatherproof protection within tested tempera- system owner's guider available containing basic information
<br /> p
<br /> tune limitations.The regulated release and tank assemblies must Pertaining to system operation and maintenance.A detailed tech-
<br /> be mounted in an area where the air temperature will not fall pical manual,including system description,design,installation,
<br /> below 32'F(0'C}or exceed 130'F(54'C),The system must be recharge and resetting instructions,and maintenance procedures,
<br /> designed and installed within the guidelines of the UUULC Listed is available to qualified individuals.
<br /> Design, Installation, Recharge,and Maintenance Manual, The system is installed and serviced by authorized distributors
<br /> that are trained by the manufacturer.
<br /> System Description The basic system consists of an AUTOMAN regulated release
<br /> assembly which includes a regulated release mechanism and
<br /> The restaurant fire suppression system is a pre-engineered,wet a wet chemical storage tank housed within a single enclosure.
<br /> chemical,cartridge-operated,regulated pressure type with a fixed Nozzles with blow-off caps,detectors,cartridges,agent,fusible
<br /> nozzle agent distribution network. It is listed with Underwriters links,and pulley elbows are supplied in separate packages in the
<br /> Laboratories, Inc. (UUULCI. quantities needed for fire suppression system arrangements.
<br /> Additional equipment includes a remote manual pull station(s),
<br /> mechanical and electrical gas valves,and electrical switches for
<br /> automatic equipment and gas line shut-off.Accessories can be
<br /> added such as alarms,warning lights,etc.,to installations where
<br /> required.
<br /> Additional tanks and corresponding equipment can be used in
<br /> multiple arrangements to allow for larger hazard coverage. Each
<br /> Q — tank is limited to a listed maximum amount of flow numbers.
<br /> 004215
<br /> y[:Q One Stanton Street / Marinette,WI 54143-2542,USA f +1-715-735-7411 I www.ansul.com
<br /> Fire Protection Products Copyright©2013Tyco Fire Products LP. 1 All rights reserved. f Form No.F-2004004-08