Laserfiche WebLink
"lC,0 x I I II Environmental Health Department <br /> - U I I�1 <br /> —COUNTY <br /> TY <br /> `c v Greomess grows here, <br /> Aboveground Petroleum Storage Act Compliance Review Report <br /> Facility Name and Address: Shell Oil Products US-Stockton Terminal, 3515 Navy Dr, STOCKTON 95203 <br /> CORRECTIVE ACTION: Ensure that facility's SPCC Plan adequately discusses procedures to test and inspect <br /> aboveground/bulk storage containers in accordance with all applicable industry standards per the 40 CFR 112.8(c)(6) <br /> requirements. The certifying professional engineer must detail in the SPCC plan the frequency and type of testing and <br /> inspections based on container size, configuration, and design based on the applicable industry standards. This discussion <br /> shall include a routine inspection schedule and forms to be used for routine inspections, applicable formal onstream and <br /> offstream inspections,testing, schedules for all tanks,frequencies, and personnel qualifications. Submit proof of correction <br /> to the EHD. <br /> This is a Class II violation. <br /> FA0003747 PR0527478 SCO21 06/30/2021 <br /> Rev.9/16/2020 Page 2 of 4 Aboveground Petroleum Storage Act Compliance Review Report <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />