Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by © Manufacturer Q Industry Standard El Professional Engineer <br /> Test Type © Pressure Q Vacuum E Hydrostatic <br /> Test Equipment Used: INCON STS <br /> Sump/UDC ID 87 STP E-85 STP UDC 3-4 UDC 7-8 <br /> Sump Manufacturer Unknown Unknown Bravo Bravo <br /> Sump Depth (inches) 56 56 24 24 <br /> Sump Bottom to Top of 12 42 16 16 <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 12:42 14:09 14:57 14:57 <br /> Initial Reading 2.8141 2.8421 2.1164 3.3209 <br /> Test End Time 12:57 14:24 15:12 15:12 <br /> Final Reading 2.8140 2.8421 2.1159 3.3208 <br /> Change in Reading 0.0001 0.0000 0.0005 0.0001 <br /> Pass/Fail Criteria +/- 0.002 +/- 0.002 +/- 0.002 +/- 0.002 <br /> Tightness Test Results Ej Pass rl Fail Ej Pass r] Fail © Pass © Fail 0 Pass EFail <br /> Sump/UDC ID <br /> Sump Manufacturer <br /> Sump Depth (inches) <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time <br /> Initial Reading <br /> Test End Time <br /> Final Reading <br /> Change in Reading <br /> Pass/Fail Criteria <br /> Tightness Test Results R7 Pass 0 Fail 0 Pass EJ Fail FEI Pass [rj Fail M Pass Ll Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3of5 <br />