VR-202-Z -31 Exhibit 2 <br /> Operability Test Procedure <br /> The Veeder-Root ISD operability test procedure provided in Exhibit 9, and in section 4 of <br /> the CARB Approved Installation, Operation and Maintenance Manual, shall be used <br /> at GDF sites to determine the operability of the Veeder-Root ISD system to comply with <br /> applicable performance standards and performance specification in CP-201 . Testing <br /> the ISD equipment in accordance with this procedure will verify the proper selection, <br /> setup and operation of the TLS Console sensors and interface modules. <br /> The Vapor Flow Meter <br /> The Veeder-Root ISD system requires one Vapor Flow Meter per dispenser installed <br /> via the CARB Approved ISD Vapor Flow Meter Manual 577013-796 for the <br /> Veeder-Root ISD System. The Vapor Flow Meter shall be installed into dispensers <br /> listed in Exhibit 1 of this Executive Order in accordance with the CARB Approved <br /> Installation, Operation and Maintenance Manual. The Vapor Flow Meter is an <br /> intrinsically safe sensor that is wired to the TLS Console Smart Sensor Module via a <br /> conduit dedicated to TLS Console low-voltage sensors. Figure 2-ISD-VR-3 shows <br /> the ISD Vapor Flow Meter. Figures 2-ISD-VR-7 and 2-ISD-VR-8 show the installation <br /> configuration. Figure 2-ISD-VR-10 shows the wireless components for Veeder-Root <br /> ISD. Figure 2-ISD-VR-11 shows a typical installation of the wireless VFM transmitter in <br /> a dispenser. <br /> The Vapor Pressure Sensor <br /> The Veeder-Root ISD system requires one Vapor Pressure Sensor per GDF installed <br /> into one of the dispensers located closest to the gasoline tanks (If a row of dispensers <br /> are equal distance from the gasoline tank pad and within 10' of each other, any <br /> dispenser can be used) in accordance with the CARB Approved Installation, <br /> Operation and Maintenance Manual. The Vapor Pressure sensor shall be installed <br /> into dispensers listed in Exhibit 1 of this Executive Order. For vapor vent stack <br /> installation, install the pressure sensor on the vent stack line closest to the tank being <br /> monitored, in accordance with Section 10 of the CARB Approved IOM Manual. The <br /> Vapor Pressure Sensor is an intrinsically safe sensor that is wired to the TLS Console <br /> Smart Sensor Module via a conduit dedicated to TLS Console low-voltage sensors. <br /> Figure 2-ISD- <br /> VR-4 shows wired and low voltage wireless ISD Vapor Pressure Sensor drawings, and <br /> the optional dryer tube drawing. Figures 2-ISD-VR-7 and 2-ISD-VR-8 show the <br /> installation configuration. Figure 2-ISD-VR-9 shows the installation configuration of <br /> the Veeder-Root vapor pressure sensor on a vapor vent stack (Note: Installation <br /> location not permitted with ARID Permeator AT-150). Figure 2-ISD-VR-10 shows the <br /> wireless vapor flow meter components. Figure 2-ISD-VR-12 shows an Overview of <br /> Veeder-Root Wireless Vapor Pressure Sensor Vent Stack Installation. <br />