Laserfiche WebLink
Testing ta vapor to liquid ratio <br /> You must use an adaptor to determine the vapor to liquid (V/L) volume ration on the <br /> HEALYTI Model 900 Series Vapor Assist Nozzle. The adaptor is required to perform a V/L ratio test <br /> with Exhibit 5 of either Executive Order VR-201 or VR-202. A V/L ratio between 0.95 and 1.15 is <br /> required (at a flow rate between 6.0 gpm to 10.0 gpm). <br /> There are three adaptors you can use to test the V/L ratio. Depending on the spout with which <br /> the nozzle you are testing is equipped, you can use the HEALYT"Adaptor Model 8034-1, the <br /> HEALYT'Adaptor Model 8034-3, or the Triangle Gold Adaptor. See the table below for correct <br /> combinations. <br /> Nozzle H EALY'"Ad a pto r HEALY"Adaptor Triangle Gold Adaptor <br /> I Model :08034-3 <br /> HEALYT"Ori inal Model 900 X X X <br /> HEALYT Model 900 with EOR Spout X X <br /> Inspect the spout seal 0-ring before you do a test. Any cuts or tears will allow air to be ingested <br /> and give an inaccurate reading. <br /> NOTE: Motor oil (any weight) is acceptable for lubricating the 0-Ring. Contact FFS Technical <br /> Support with any questions about other lubricants you can use when you do this test. <br /> STEP #1—INSERT SPOUT TIP UNTIL <br /> HEALY LOGO ON SPOUT ANCHOR RING HITS STOP <br /> BOOT FACE SEAL <br /> SPOUT LOCKING <br /> THUMB SCREW <br /> STEP #3—INSERT PINS <br /> D3LEED HOLES TO SEAL SPOUT SEAL <br /> VELCRO STRAP GASOLINE <br /> TEST TAP <br /> - I <br /> SPOUT ADAPTER <br /> I ASSEMBLY <br /> I <br /> 3/4" to 1" I. D. <br /> TUBE CONNE^ <br /> TO ROOTS M <br /> (MAX. LENGI <br /> I <br /> STEP #4— <br /> ATTACH MAGNETtROOTS <br /> VAPOR FROM <br /> ASSEMBLY METER <br /> MODEL 900 NOZZLE <br /> w <br /> CARB approved IOM 2-HEAL r 900 Nozzle Series-Executive Orders VR-201 and VR-202 <br />