ARID PERMEATOR INSTALLATION NOTES PERMEATOR INSTALLATION TASKS: <br /> 1,PHYSICAL CONNECTION: PERMEATOR REQUIRES A 2 INCH LINE FOR FEED,RETENTATE(EXHAUST)AND PERMEATE RETURN LINES ARID SUPPLIES 2,6 INCH ANSI 125 1.MOUNT ELECTRICAL CONTROL CABINET WITHIN CONTROLLER ENCLOSURE. ��pp <br /> 4-BOLT FLANGES; INSTALL CONTRACTOR PROVIDES THE MATING 6 INCH FLANGES.THE TWO(2)FEED AND PERMEATE LINES ARE PIPED TO THE VERTICAL VENT RISERS 2 M <br /> USING A"T"AND 90 DEGREE ELBOW AS A"SWING JOINT".ARID ALSO RECOMMENDS THAT LOW RESISTANCE,STRAIGHT-THROUGH BALL VALVES BE INSTALLED BETWEEN THE 2.ENSURE PRESENCE OF A DEDICATED TELEPHONE LINE JACK WITHIN 6 FEET OF ELECTRICAL CONTROL PANEL. O Q <br /> FLANGES AND VENT RISERS ON THE FEED AND PERMEATE RETURN LINES.TYPICALLY,THE RETENTATE(EXHAUST)LINE IS RUN PARALLEL TO THE VENT RISERS AND F W <br /> BRING MAIN POWER TO CONTROL PANEL AND POWER/CONTROL SIGNAL WIRING FROM CONTROL PANEL TO PERMEATOR _J Z <br /> SUPPORTED WITH UNI-STRUT.IN ADDITION,THE TOP OF THE RETENTATE LINE IS FITTED WITH A RAIN-CAP(NOT A P/V VALVE). 3.LOCATED ALONGSIDE VENT PIPES.POWER IS 208 V/60 HE /3 PHASE; 20 AMP SERVICE REQUIRED.CONTROL J ED <br /> J Z J <br /> THE FOUR LEGS ON EACH PERMEATOR ARE FORMED WITH HOLES TO ACCOMMODATE RED-HEAD MOUNTING BOLTS TO THE CEMENT PAD LOCATED ADJACENT TO THE VENT WIRING IS 24 VOLT DC(4-20 MA); SIGNAL WIRES SHOULD BE SHIELDED 18 OR 20 AWG CABLE; 1 PAIR,OR 2 "Q p ir 2 U <br /> PIPE RISERS. CONDUCTORS PER EACH SENSOR SIGNAL.PERMEATOR EQUIPPED WITH DATA LOGGER REQUIRES 3 SIGNALS OR 6 _ Z Z w O LL <br /> CONDUCTORS.SEPARATE CONDUITS SHOULD BE USED FOR POWER AND COMMUNICATION CABLES,RESPECTIVELY. w <br /> 2.NON-HYDROCARBON SENSOR VERSION--ELECTRICAL: ARID RECOMMENDS USING TWO(2)RIGID CONDUITS.THE FIRST CONDUIT IS FOR RUNNING 3 PAIRS(6 CONDUCTORS) e ¢ Z m LL Z <br /> OF SHIELDED 18 GAUGE CABLE.THE CONTROL CIRCUIT VOLTAGE IS 24 V DC,AND CURRENT IS 4-20 MILLIAMPS.THE SECOND CONDUIT IS FOR RUNNING POWER WIRES: 208 4.POUR 5 FT.X 5 FT.CEMENT PAD ALONGSIDE VENT PIPES AND MOUNT PERMEATOR WITH 4 BOLTS THROUGH THE U Q=Q J <br /> V,3 PHASE,60 HZ,20 AMPS; 3 CONDUCTORS(12 OR 14 AWG OR LOCAL CODE)PLUS ONE GROUND WIRE.THESE CONDUITS WILL RUN BETWEEN THE CONTROL PANEL EXISTING SUPPORT STAND LEGS,PERMEATOR MAIN CABINET WEIGHT IS APPROXIMATELY 750 LBS AND FOUR LEGGED RQ W F U U <br /> LOCATED IN THE CONTROLLER ENCLOSURE HOUSING THE SUBMERSIBLE TURBINE PUMP ELECTRONICS AND A JUNCTION BOX LOCATED ON THE PAD ADJACENT TO OR BASE MEASURES 36 INCHES X 36 INCHES. a W J N N <br /> MOUNTED ON THE PERMEATOR.THE JUNCTION BOX ON THE PAD WILL COMMUNICATE WITH THE MOTOR OF THE PERMEATOR AND AN ADDITIONAL PERMEATOR MOUNTED IS W Q Q z Q <br /> JUNCTION BOX THROUGH A FLEXIBLE BRANCH CONDUIT OF 3/4 INCH DIAMETER. (TYPICALLY,THESE CONDUITS MAKING FINAL CONNECTIONS BETWEEN RIGID CONDUIT AND .5.CONNECT 2 INCH FEED AND RETURN PIPING TO VENT RISERS; PROVIDE LOW RESISTANCE("STRAIGHT-THROUGH")BALL e W W 0 <br /> MOTOR/CONTROL WIRE JUNCTION BOXES ARE WATER-TIGHT FLEXIBLE CONDUITS,RATED FOR HAZARDOUS AREAS) VALVES FOR ISOLATION AND SHUT-OFF ON THE FEED AND PERMEATE RETURN LINES,AND PIPE VAPOR RETURN LINE s IL 00 U <br /> TO LOW GRADE PRODUCT VENT.PLACE A 2 INCH"Y'BETWEEN THE FLANGE CONNECTION AND THE ISOLATION BALL O <br /> THE ELECTRICAL CONTROL PANELS ARE 18"WIDE X 20"LONG X 8"DEEP AND ARE MOUNTED IN THE CONTROLLER ENCLOSURE HOUSING THE PUMP ELECTRONICS.THE VALVE ON THE RICH VAPOR RETURN LINE.ENSURE MINIMUM SLOPE OF 1/4 TO 1/8 INCH PER FOOT FROM S <br /> CONTROL PANEL HAS AN INTEGRAL POWER SUPPLY FOR THE CONTROL CIRCUITS,AND ACCEPTS THE 208 V,3 PHASE,60 HZ MAIN POWER.(PERMEATOR REQUIRES A 20 PERMEATOR TO VENT RISERS. <br /> AMP CIRCUIT). <br /> a <br /> 6.CONNECT EXHAUST VENT TO PERMEATOR AND SUPPORT BY RUNNING PARALLEL TO EXISTING VENT RISERS,AND CAP R <br /> INSTALL RATED LOCAL DISCONNECT SWITCH LOCATED NOT WITHIN 18"HORIZONTALLY FROM THE UNIT AND AT LEAST 18"ABOVE GRADE FOR EQUIPMENT MAINTENANCE PURPOSES. THE EXHAUST VENT WITH A FRESH AIR VENT CAP. <br /> PERMEATOR UNIT CIRCUITRY SHALL BE TED INTO THE EMERGENCY SHUTOFF SWITCH CIRCUITRY SUCH THAT IN THE EVENT OF AN EMERGENCY SHUTDOWN,POWER WILL BE CUT TO THE <br /> CONTROL PANEL IN THE CONTROLLER ENCLOSURE AND TO THE MOTORS AT THE PERMEATOR UNIT. 7.ARID PERSONNEL TO OVERSEE WIRING TERMINATION CONNECTIONS WITH ELECTRICIAN IN THE FIELD. SIV£ <br /> SEE SHEET T4-1 <br /> FOR PIPING DETAILS <br /> DPW 723V VENT CAP 2 <br /> INSTRUMENT MOUNTING PLATE EMCO WH"To <br /> N 3 <br /> 2S X 13'X 1/4"THK. ATMOSPHERIC NR CAP <br /> #A4103-002 <br /> OIL FILL CA CLEAN AIR VALV <br /> 361, MEMBRANE MODUL <br /> 38.1]M899in0 ERALL 1 <br /> PRESSURE RELIEF VALV W <br /> m <br /> P 15.8]51n W¢m <br /> D °°3 <br /> RE SIDS VACUUM PUMP O =W <br /> W/SHIP TEXP RELIANCE MOTO O 3 Y= <br /> CLEAN AIR OUTLET, Q J Q <br /> 3Bin ENCLOSURE W/LOGKABLU <br /> 4.5in ODORS AND VENTS 1 NPT F Q O <br /> 41.1311mOVERALL <br /> 0 N <br /> V TEE AND 1/d" <br /> TEST PORT <br /> din <br /> :IB ED- <br /> 3in <br /> 0 2 O F S <br /> 0 4 VS THRIL •y <br /> OIL FILL CA SECTION AO O rtrtrtRRRRIiii <br /> SCALE 1:d <br /> GROUND FOOT PAD DETAIL O O <br /> CONNECTIG�­3 <br /> TYPICAL-d PLACES <br /> O <br /> OIL SIGHT BOTH PIERS 1/8" <br /> PER FOOT DOOWNWN <br /> OILDRAI OR <br /> VENT <br /> 58.625in OUTLET(RICH GASOLINOAIR nnlm VP'♦:,M <br /> RETURN OTANK), f <br /> 2"42WANSIFF.BY.G.C. <br /> 21 2"BOLL VALVE INLET(LEAN s]3 O�ViL \ <br /> (TYP.OF 2) GASOLINE/AIR FROM q'Opp 1 <br /> TANK),Y-125PANSI F.F. <br /> 31.2981891n 2 P ACES BY.G.F gg N <br /> g <br /> • F P � R <br /> 30.25in ® f � 4 <br /> t <br /> .I, 8 <br /> 8.95]33in lin e C �, <br /> 30.]]16535, a ,� <br /> 65.25H OVE LL •C R <br /> © Wryryry s <br /> DRIP PAN DRAIN C a <br /> (PLUGGED) <br /> .330]08]In <br /> ]118' C Ma .ry g <br /> 36in �U g y�X�Ii <br /> EXUWER <br /> NOTE:ARID TECHNOLOGIES PERMBATOR TO BE <br /> COND 111,V N T LOCATED IN CONFORMANCE WITH MANUFACTURERS <br /> W11 SATNPT LDCATEAPON MANUAL.CARB II WINO ORURE <br /> DRAIN(PLUGGED) AND ALL APPLICABLE STATE AND LOCO CODES, <br /> NDTE:AODRIONAL SCREEN WALL OR CONSTRUCTION g <br /> 1 MAV BE REQUIRED BY LOCAL ORDINANCES.VERIFY <br /> 1_ REOUIREMEMS WITH ARCHITECT.MINIMUM MOUNTING <br /> 1 REOUIREMEMS ARE SHOWN IN THIS DETAIL. <br /> STING L—L -k-NER -IE1111_1�l <br /> "I 1PRAN <br /> e <br /> 3in - - 3DIn 4X0&B'THRU MEMBRANE MODULE HOUSING,834 TALL STAND DIMENSIONAL TLNETO TO REMMN 9RION <br /> OR REI-N F <br />