VR-202-Z -35 Exhibit 1 <br /> SECTION II - In-Station Diagnostics <br /> Option 1 -Veeder-Root Equipment (VR) <br /> Component Manufacturer/Model <br /> TLS Console <br /> TLS-350 <br /> TLS-350 Plus TLS-350R <br /> Red Jacket ProMax <br /> Gilbarco EMC <br /> Simplicity <br /> Veeder-Root 8482XX-XXX <br /> Veeder-Root 8470XX-XXX X =Any digit <br /> (Figure 1-ISD-VR-1) <br /> ISD Software Version <br /> Veeder-Root ISD 1.0626 <br /> (Required for new installations and facilities <br /> undergoing major modification) <br /> Refer to Table 1-ISD —VR-1, Veeder-Root ISD Software <br /> Version Compatibility Matrix <br /> Vapor Flow Meter <br /> (1 per Dispenser) <br /> Veeder-Root 331847-XXX <br /> X =Any digit <br /> (Figure 1-ISD-VR-2) <br /> Vapor Pressure Sensor <br /> (1 per GDF) <br /> Veeder-Root 331946-001 or 861190-20127 <br /> Wired, approved for installation in the dispenser or on <br /> the vent stack <br /> (Figure 1-ISD-VR-3a) <br /> OR <br /> Veeder-Root 861190-201 <br /> Low Powered Wireless, approved for installation on the vent <br /> stack ONLY <br /> (Figure 1-ISD-VR-3b) <br /> 26 ARID Permeator AT-150 installations must be done with Version 1.06 software. Clean Air Separator installations can use previous <br /> versions, but Version 1.06 software is compatible with both Permeator AT-150 and Clean Air Separator. <br /> 2'For installations using the ARID Permeator AT-150, only dispenser mounted ISD transducer is approved. <br />