Laserfiche WebLink
SAN JOA U I Environmental Health Department <br /> C)U NT `f <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> TIWANA GAS & FOOD 1 1210 E HAMMER LN, STOCKTON June 14, 2021 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 306 HSC 25291(e) Failure to remove, analyze, and properly dispose of water in secondary containment(pre-Jul 2003). <br /> OBSERVATION: Liquid was observed in the diesel fill sump. <br /> REGULATION GUIDANCE: If water could enter into the secondary containment by precipitation or infiltration, it must <br /> be removed and disposed of properly. <br /> CORRECTIVE ACTION: The service technician removed 1 gallon of liquid from the diesel fill sump. Ensure that all <br /> sumps and annular spaces are maintained free of liquid. <br /> This is a repeat violation, Class II. <br /> 318 CCR 2635, 2637.1, 2665, 2712 Failed to meet spill container requirements. <br /> OBSERVATION: The 87, 91 spill containers failed when tested. <br /> REGULATION GUIDANCE: All spill containers shall have a minimum capacity of five gallons and be capable of <br /> containing a spill or overfill until it is detected or cleaned up. <br /> CORRECTIVE ACTION: Immediately contact a properly licensed, trained, and certified contractor to repair or <br /> replace the spill container under permit and inspection of the EHD. <br /> This is a repeat violation, Class II. <br /> Overall Inspection Comments: <br /> An inspection checklist was provided to the facility operator on the day of inspection, 6/14/2021. A complete <br /> report was finished on 6/15/2021 and replaces the initial checklist. <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, within 30 days of receiving the complete inspection report. <br /> Documents provided; EHD class schedule, and return to compliance form. <br /> AFTER THE COMPLIANCE DATE, EHD WILL BILL FOR ALL TIME AND ACTIVITIES ASSOCIATED WITH BRINGING THIS <br /> FACILITY BACK INTO COMPLIANCE. <br /> THIS FACILITY IS SUBJECT TO REINSPECTION AT ANY TIME AT EHD'S CURRENT HOURLY RATE. <br /> Received by: Date: June 15, 2021 Inspector: Inspector Phone: <br /> Printed Name and Title: FREDERICK ERNEST, EHS Trainee (209) 616-3026 <br /> Chris Slates, Manager <br /> FA0003730 PR0231125 SCO01 06/14/2021 <br /> EHD 23-01 Rev.9/16/2020 Page 7 of 7 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />