Laserfiche WebLink
Underground Storage Tank <br /> Overfill Prevention Equipment Inspection Report <br /> 6. OVERFILL PREVENTION EQUIPMENT DETAILS <br /> T4 RUL T5 MUL <br /> Tank ID (one OPE per column) <br /> Are both vent and tank riser piping Yes Yes r Yes r Yes <br /> secondarily contained? r No r No r- No r- No <br /> OPE Model oPW oPW <br /> VShut off ,V Shut off Shut off Shut off <br /> Flow Flow Flow Flow <br /> Restricts Restricts Restricts Restricts <br /> What is the OPE response when activated? Flow Flow Flow Flow <br /> (Check all that apply) Audible Audible Audible Audible <br /> Alarm Alarm Alarm Alarm <br /> F Visual Visual Visual Visual <br /> Alarm Alarm Alarm Alarm <br /> Are flow restrictors installed on vent piping r Yes* r Yes* r Yes* r Yes* <br /> that may interfere with the OPE operation? l: No r: No r No r No <br /> At what level in the tank is the OPE set to <br /> activate? (Inches from bottom of tank) 80.875 76.75 <br /> What is the percent capacity of the tank at <br /> which the OPE activates? 94.8 91.7 <br /> Is the OPE in proper operating condition to r Yes Yes r' Yes r' Yes <br /> respond when the stored substance reaches r No r No r No r No <br /> the designated regulatory level? <br /> 7. SUMMARY OF TESTING RESULTS <br /> OPE Inspection Results r Pass Pass r Pass r Pass <br /> r Fail r Fail r Fail r Fail <br /> 8. COMMENTS <br /> Describe all results marked "Fail"and each proposed remedy. <br /> COULDNT REMOVE PREM. DROPTUBE <br /> *Mark here if: <br /> Flow restrictors interfere with overfill prevention and equipment repairs required. <br /> Additional copies of this page may be attached. <br /> Attach tank chart(s), measurements, calculations, and In-Tank Setup report(s) <br />