Laserfiche WebLink
The following is an itemized list of underground storage tank violations that have not <br />been addressed for STOP N SHOP as of February 09, 2021. <br />Open violations from August 31, 2020 inspection <br />Violation #319 - Failure to comply with the installation, inspection, or record keeping of the overfill <br />prevention. <br />OBSERVATION: Overfill prevention testing has not been conducted. <br />REGULATION GUIDANCE: Overfill prevention equipment inspections were required to be conducted by October <br />13, 2018, and every 36 months thereafter, and within 30 days of completion of a repair. <br />CORRECTIVE ACTION: Immediately schedule this testing and provide 48 hours notification to the EHD. Ensure all <br />future testing is conducted within required time frames. <br />❑ This violation was corrected ❑ This violation will be corrected by (date): <br />❑ Supporting documents included <br />Describe actions taken or will be taken to correct violation: <br />Page 9 of 9 <br />