ISD ALARM STATUS REPORT <br /> EVR TYPE: BALANCE <br /> ISD TYPE: 01.05 <br /> VAPOR PROCESSOR TYPE: NONE <br /> OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS <br /> EVR VAPOR CONTAINMENT :PASS <br /> ISD MONITOR UP-TIME :100% <br /> EVR/ISD PASS TIME :100% <br /> WARNING ALARMS <br /> DATE TIME DESCRIPTION READING VALUE <br /> 21-04-28 10:02:28 FLOW PERFORMANCE HOSE BLOCKAGE FP 8 BLENDS 0.55 <br /> 21-02-17 10:01:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 13.62 <br /> 21-02-16 10:01:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 13.80 <br /> 21-01-31 10:01:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 13.92 <br /> 21-01-28 10:01:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 13.54 <br /> 21-01-09 10:01:09 SENSOR OUT SELFTEST E 1 <br /> 21-01-08 10:01:09 SENSOR OUT SELFTEST E 1 <br /> 21-01-07 10:01:09 SENSOR OUT SELFTEST E 1 <br /> 21-01-06 10:01:09 SENSOR OUT SELFTEST E 1 <br /> 21-01-05 10:01:09 SENSOR OUT SELFTEST E 1 <br /> FAILURE ALARMS <br /> DATE TIME DESCRIPTION READING VALUE <br /> 21-01-11 10:01:09 SENSOR OUT SELFTEST E 1 <br /> 21-01-10 10:01:09 SENSOR OUT SELFTEST E 1 <br /> 20-11-16 10:01:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 59.58 <br /> 20-10-19 10:01:09 FLOW PERFORMANCE HOSE BLOCKAGE FP12 BLENDS <br /> 20-04-28 08:13:32 A/L RATIO DEGRADATION FP10 BLENDS 0.80 <br /> 19-02-04 10:00:46 A/L RATIO GROSS BLOCKAGE FP 9 BLENDS BLKD <br /> 19-01-06 10:00:44 A/L RATIO DEGRADATION FP12 BLENDS 0.82 <br /> 18-10-29 10:00:21 A/L RATIO DEGRADATION FP 7 BLENDS 0.72 <br /> 18-02-25 10:02:20 A/L RATIO GROSS BLOCKAGE FP 7 BLENDS 2.14 <br /> 17-12-20 10:01:13 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.93 <br /> SHUTDOWN & MISCELLANEOUS EVENTS <br /> DATE TIME DESCRIPTION ACTION/NAME <br /> 21-06-22 11:30:36 CONTAINMENT VAPOR LEAKAGE TEST MANUALLY CLEARED <br /> 21-06-22 11:30:32 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED <br /> 21-06-22 10:52:03 READINESS ISD:PP EVR:NN EVR READINESS PENDING <br /> 21-06-22 10:52:03 ISD STARTUP <br /> 21-06-22 10:51:36 ISD SHUTDOWN <br /> 21-03-14 03:00:00 TIME CHANGE DETECTED AT: 21-03-14 02:00:13 <br /> 21-02-17 12:23:24 CONTAINMENT VAPOR LEAKAGE TEST MANUALLY CLEARED <br /> 21-01-29 10:01:09 READINESS ISD:PP EVR:PP ISD & EVR READY <br /> 21-01-28 10:01:09 READINESS ISD:PP EVR:PF CHECK EVR SYSTEM <br /> 21-01-27 12:40:48 READINESS ISD:PP EVR:NN EVR READINESS PENDING <br />